College, university building HVAC design

College and university campus buildings have a lot going on—classes, research, dining, and sleeping. HVAC and air quality are key aspects of these buildings.

12/19/2013


Robert Garra, PE, CDT is Vice president, electrical engineering of Cannon Design, Buffalo, N.Y. Courtesy: Cannon DesignRandy Hassler, PE, LEED AP is a Principal at McClure Engineering, St. Louis, MO. Courtesy: McClure EngineeringAndrew Slater, PE, is an electrical engineer at HGA Architects and Engineers in Milwaukee, WI. Courtesy: HGA Architects and Engineers

Participants

Robert Garra, PE, CDT, Vice president, electrical engineering, Cannon Design, Buffalo, N.Y.

Randy Hassler, PE, LEED AP, Principal, McClure Engineering, St. Louis, MO

Andrew Slater, PE, Electrical engineer, HGA Architects and Engineers, Milwaukee, WI


CSE: What unique requirements do college and university HVAC systems have that you wouldn’t encounter on other structures?

McClure Engineering’s team replaced outdated systems at Washington University in St. Louis; new equipment included a 2,200-ton central chiller plant, three regional hot water boiler plants, and a host of utility infrastructure. Courtesy: McClure EngineeriHassler: Campuses can have many different building types, or types of spaces within the buildings: offices, classrooms, laboratories, libraries, museums, data centers, clean rooms, housing, dining, performance arts, radio station, recreation complex, health care, police station, hazardous waste disposal, power plants, etc. The basic equipment (i.e., pumps, fans, air handling units, heat exchangers) that comprise the systems are similar; however, the diversity of building types requires being grounded in the fundamentals and having knowledge of the nuances of different applications. 

CSE: How can automated features and remote system control benefit campus clients? 

Hassler: Campus buildings, while having nominal occupancy schedules, can be occupied at all hours of the night by facility, researchers, or students. Occupancy sensors can be used to change the “mode” of the zone or system. Often people think of using occupancy sensors only for two states, occupied or unoccupied. There can be four states: normal hours—occupied or unoccupied; and after hours—occupied or unoccupied. This would be an example for an office VAV box with reheat:

  • Normal hours, occupied: minimum cfm for ventilation, space temp setpoint by thermostat.
  • Normal hours, unoccupied: cooling minimum cfm = 0, space temp setpoint 75 F cooling and 70 F for heating. (Strategy is to save reheat when unoccupied and keep the space within a comfortable dead band temperature range. You would not want to return from a meeting to an 85 F office and have to wait for it to cool down.)
  • After hours, occupied: space temp setpoint 75 F cooling and 70 F for heating.
  • After hours, unoccupied: cooling minimum cfm = 0, space temp setpoint 85 F cooling and 60 F for heating. 

CSE: In general, what payback period do colleges and universities expect? 

Hassler: Typically longer than other clients, 10 or more years because they own and operate their buildings for a long time. Many owners also want to consider lifecycle cost considering energy, system life, maintenance, and end-of-life replacement cost in the evaluation.



Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
November 2018
Emergency power requirements, salary survey results, lighting controls, fire pumps, healthcare facilities, and more
October 2018
Approaches to building engineering, 2018 Commissioning Giants, integrated project delivery, improving construction efficiency, an IPD primer, collaborative projects, NFPA 13 sprinkler systems.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me