Breaker Discrimination in the Computer Room

A dynamic technological breakthrough was needed to solve the inevitable problem of circuit breaker discrimination in panel boards. This is especially a concern in mission-critical operations. It was certainly the case for Bank One, when it teamed with New York City-based EYP Mission Critical Facilities, Inc.

11/01/2003


A dynamic technological breakthrough was needed to solve the inevitable problem of circuit breaker discrimination in panel boards. This is especially a concern in mission-critical operations. It was certainly the case for Bank One, when it teamed with New York City-based EYP Mission Critical Facilities, Inc., to overcome this downtime vulnerability in Bank One's new corporate data centers, where there are numerous business lines fed from each computer room panel board.

At locations where distribution is typically through 42-circuit panel boards—what is referred to in computer room vernacular as a remote power panel (RPP)—a short on a branch circuit that also trips the upstream panel main breaker would result in the loss of 42 or more processes or end users. Today's panel board circuit breakers are molded case UL 489 products that respond to peak currents during a short-circuit event.

The Bank One design team considered replacing the RPP's main circuit breakers with "non-automatic switches." However, switches would trip automatically for a high current condition because of fixed magnetic trip elements intended to self protect these products from a thermal runaway.

Actually, switches offer little improvement over a standard circuit breaker; both will trip at approximately 10X. Fused branch circuits were evaluated but also ruled out, based on the fact that the size of fused panel boards is about 2:1 in comparison to circuit breaker panel boards.

Also, "blow open" branch breakers, which clear a fault within eight milliseconds, were researched and found to be as fast as fuses.

Finally, the design team learned about a recently developed mission-critical breaker that is a hybrid of the company's type-LA molded case circuit breaker, a technology that has been a tried and proven workhorse of many critical sites for years. When used as a panel main, it delivers selective tripping for short-circuit conditions. This applies to panel boards incorporating 20- to 100-amp single- and three-phase branch circuits and the breaker as the main.

The high magnetic trip setting on these breakers will allow, for example, a 250-amp main panel circuit breaker to hold or "stay closed" while a fault downstream of a 30-amp branch is cleared by the branch breaker. The upstream 250-amp breaker will not trip.





Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
June 2018
Chilled-water system design, NFPA 99, Grounded power supply systems
May 2018
40 Under 40 winners, fire and life safety, performance-based designs, and more
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me