Author Notes Table Snafu in Article

Reading over "Playing the Smart Hand" (Jan. 2001, p. 42), I noticed that Table 3, Chiller Algorithm Output, was not the latest one that I had sent with my article revision.The electric chiller calculation that was shown on the table in the magazine was missing the kilowatt/ton in the formula.Kent W.

02/01/2002


Reading over "Playing the Smart Hand" (Jan. 2001, p. 42), I noticed that Table 3, Chiller Algorithm Output, was not the latest one that I had sent with my article revision.

The electric chiller calculation that was shown on the table in the magazine was missing the kilowatt/ton in the formula.

Kent W. Peterson, P.E., Chief Mechanical Engineer and Principal, P2S Engineering, Long Beach, Calif.

Chiller Algorithm Output

Example 1 Example 2 Example 3
Gas ($/therm)$ 0.35$ 0.35$ 0.35
Electric ($/kWh)$ 0.05$ 0.12$ 0.18
Plant Load (Tons) Best Chiller Combination Cost/Ton-Hr Best Chiller Combination Cost/Ton-Hr Best Chiller Combination Cost/Ton-Hr
4002$0.0311$0.0661$0.075
5002$0.0291$0.0571$0.065
6002$0.0282$0.0683$0.089
7002$0.0282$0.0683$0.082
8002$0.0283$0.0663$0.075
9002$0.0293$0.0613$0.069
1,0005$0.0293$0.0573$0.065
1,1005$0.0294$0.0684$0.094
1,2005$0.0284$0.0674$0.093
1,3005$0.0284$0.0664$0.092
1,4005$0.0284$0.0676$0.092
1,5005$0.0286$0.0686$0.090
1,6005$0.0286$0.0676$0.088
1,7005$0.0286$0.0666$0.087
1,8005$0.0296$0.0656$0.086
1,9005$0.0306$0.0656$0.087
2,0005$0.0316$0.0666$0.088





Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me