ASHRAE’s new energy standard for data centers 

ASHRAE Standard 90.4 is a flexible, performance-based energy standard that goes beyond current ASHRAE 90.1 methodology.

07/19/2017


Learning objectives:

  • Explain ASHRAE Standard 90.1. This article is peer-reviewed.
  • Understand the fundamentals of ASHRAE Standard 90.4. 
  • Explore how ASHRAE 90.4 will impact data center mechanical/electrical system design. 

The data center industry is fortunate to have many dedicated professionals volunteering their time to provide expertise and experience in the development of new guidelines, codes, and standards. ASHRAEU.S. Green Building Council, and The Green Grid, among others, routinely call on these subject matter experts to participate in working committees with the purpose of advancing the technical underpinnings and long-term viability of the organizations’ missions. For the most part, the end goal of these working groups is to establish consistent, repeatable processes that will be applicable to a wide range of project sizes, types, and locations. For ASHRAE, this was certainly the case when it came time to address the future of the ASHRAE 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings vis-à-vis how it applies to data centers. 

ASHRAE Standard 90.1 and data centers  

ASHRAE 90.1 has become the de facto energy standard for U.S. states and cities as well as many countries around the world. Data centers are considered commercial buildings, so the use of ASHRAE 90.1 is compulsory to demonstrate minimum energy conformance for jurisdictions requiring such. Specific to computer rooms, ASHRAE 90.1 has evolved over the last decade and a half, albeit in a nonlinear fashion. The 2001, 2004, and 2007 editions of ASHRAE 90.1 all have very similar language for computer rooms, except for humidity control, economizers, and how the baseline HVAC systems are to be developed. It is not until the ASHRAE 90.1-2010 edition where there are more in-depth requirements for computer rooms. For example, ASHRAE 90.1-2010 contains a new term, “sensible coefficient of performance” (SCOP), an energy benchmark used for computer and data processing room (CDPR) air conditioning units. The construct of SCOP is dividing the net sensible cooling capacity (in watts) by the input power (in watts). The definition of SCOP and the detail on how the units are to be tested comes from the Air Conditioning, Heating, and Refrigeration Institute (AHRI) in conjunction with the American National Standards Institute (ANSI) and was published in AHRI/ANSI Standard 1360: Performance Rating of Computer and Data Processing Room Air Conditioners

With the release of ASHRAE 90.1-2013, additional clarification, and requirements related to data centers including information for sizing water economizers and an introduction of a new alternative compliance path using power-usage effectiveness (PUE) were included. As a part of the PUE alternate compliance path, cooling, lighting, power distribution losses, and information technology (IT) equipment energy are to be documented individually. But since the requisites related to IT equipment (ITE) listed in ASHRAE 90.1 were originally meant for server closets or computer rooms that consume only a piece of the energy of the total building, there were still difficulties in demonstrating compliance. Yet there was no slowdown in technology growth; projects began to slowly include full-sized data centers with an annual energy usage greater than the building in which they are housed. Even with all the revisions and additions to ASHRAE 90.1 relating to data centers, there were still instances that proved difficult in applying ASHRAE 90.1 for energy-use compliance. Figure 1:In Washington State, climate analysis forSeattle shows relatively mild dry-bulb temperatures through the year with little variation. All graphicscourtesy: exp

Fortunately, as the data center community continued to evolve in terms of sophistication in designing and operating highly energy-efficient facilities, so did ASHRAE 90.1 with the release of the 2013 edition. But even before ASHRAE 90.1-2013 was released, the data center community was pushing for clearer criteria for energy-use compliance. It was crucial that these criteria would not stifle innovation, but at the same time provide logic and consistency on how to comply with ASHRAE 90.1. Many in the data center engineering community (including ASHRAE) knew something needed to change. 

ASHRAE Standard 90.4-2016 

Given the long history of ASHRAE 90.1 (dating back to 1976) and its demonstrated effectiveness in reducing energy use in buildings, several questions needed to be addressed before new criteria could be developed. What would be the best way to develop new language for data center facility energy use? Should it be an overlay to the existing standard? Should it be a stand-alone document? Should it be a stand-alone document and duplicate all the language in ASHRAE 90.1? How should the technical processes developed by The Green Grid and U.S. Green Building Council be folded into the standard? Would it be able to keep up with the fast-paced technology developments that are truly unique to data centers? 

Fast-forward a few years and in mid-2016, ASHRAE published ASHRAE 90.4-2016: Energy Standard for Data Centers. Coming in at just 68 pages, ASHRAE 90.4 doesn’t seem to be as detailed as compared with other standards released by ASHRAE (ASHRAE 90.1 weighs in at just over 300 pages). But this is by design—instead of trying to weave in data center-specific language into the existing standard, ASHRAE wisely chose to create a (mostly) stand-alone standard that is only applicable to data centers and contains references to ASHRAE 90.1. These references mainly are for building envelope, service-water heating, lighting, and other requirements. Using this approach avoids doubling up on future revisions to the standard, minimizes any unintended redundancies, and ensures that the focus of ASHRAE 90.4 is exclusive to data center facilities. Also, issuing updates to ASHRAE 90.1 will automatically update ASHRAE 90.4 for the referenced sections. In the same way, updates to ASHRAE 90.4 will not affect the language in ASHRAE 90.1. Using ASHRAE 90.1 will not automatically require the use of ASHRAE 90.4. In fact, since many local jurisdictions operate on a 3-year cycle for updating their building codes, many are still using the ASHRAE 90.1-2013 or earlier. The normative reference in ASHRAE 90.4 is ASHRAE 90.1-2016; however, the final say on an administrative matter like this will always fall to the authority having jurisdiction (AHJ). 

Fundamentals of ASHRAE 90.4  Figure 2: Climate analysis forthe city ofSeattle shows dew point temperatures indicatingelevated moisture levels.

ASHRAE 90.4 gives the engineer a completely new method for determining compliance. ASHRAE introduces new terminology for demonstrating compliance: design and annual mechanical load component (MLC) and electrical-loss components (ELC). ASHRAE is careful to note that these values are not comparable to PUE and are to be used only in the context of ASHRAE 90.4. The standard includes compliance tables consisting of the maximum load components for each of the 19 ASHRAE climate zones. Assigning an energy efficiency target, either in the form of design or an annualized MLC to a specific climate zone, will certainly raise awareness to the inextricable link between climate and data center energy performance (see figures 1 and 2). Since strategies like using elevated temperatures in the data center and employing different forms of economization are heavily dependent on the climate, an important goal is to increase the appreciation and understanding of these connections throughout the data center design community. 

Design mechanical-load component 

MLC can be calculated in one of two ways to determine compliance. The first is a summation of the peak power of the mechanical components in kilowatts, as well as establishing the design load of the IT equipment, also in kilowatts. ASHRAE 90.4 has a table of climate zones with the respective design dry-bulb and wet-bulb temperatures that are to be used when determining the peak mechanical system load. The calculation procedure is shown below. It must be noted that when comparing the calculated values of design MLC, the analysis must be done at both 100% and 50% ITE load; both values must be less than or equal to the values listed in Table 6.2.1 (design MLC) in ASHRAE 90.4. 

Design MLC=[cooling design power (kW)+pump design power (kW)+heat rejection design fan power (kW)+air handler unit design fan power (kW)]÷data center design ITE power (kW)

Annualized mechanical-load component 

The concepts used for the annualized MLC path are like the design MLC, except an hourly energy analysis is required when using the annualized MLC path.  

This energy analysis must be done using software specifically designed for calculating energy consumption in buildings and must be accepted by the rating authority. Some of the primary requirements of the software include the dynamic characteristics of the data center, both inside and outside. The following are some of the software requirements used in the modeling: 

  • Test in accordance with ASHRAE Standard 140: Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs
  • Able to evaluate energy-use status for 8,760 hours/year. 
  • Account for hourly variations in IT load, which cascades down to electrical system efficiency, cooling system operation, and miscellaneous equipment power. 
  • Include provisions for daily, weekly, monthly, and seasonal building-use schedules. 
  • Use performance curves for cooling equipment, adjusting power use based on outdoor conditions as well as evaporator and condenser temperatures. 
  • Calculate energy savings based on economization strategies for air- and water-based systems. 
  • Produce hourly reports that compare the baseline HVAC system to a proposed system to determine compliance with the standard.  
  • Calculate required HVAC equipment capacities and water- and airflow rates. 

Since ASHRAE 90.4 categorizes compliance metrics based on climate zone, it is imperative that the techniques used in simulating the data center’s energy use are accurate based on the specific location of the facility. As such, the simulation software must perform the analysis using climatic data including hourly atmospheric pressure, dry-bulb and dew point temperatures as well as wet-bulb temperature, relative humidity, and moisture content. This data is available from different sources and in the form of typical meteorological year, (TMY2, TMY3), and EnergyPlus Weather (EPW) files that are used as an input to the main simulation program. 

This compulsory hourly energy-use simulation considers fluctuations in mechanical system energy consumption, particularly in cases where the equipment is designed for some type of economizer mode, as well as energy reductions in vapor-compression equipment from reduced lift due to outdoor temperature and moisture levels. This approach seems to be the most representative of determining the energy performance of the data center, and since it is based on already established means of determining building energy use (i.e., hourly energy-use simulation techniques), it also will be the most understandable. Again, it must be noted that when comparing the calculated values of annualized MLC, the analysis must be done at both 100% and 50% ITE load; both values must be less than or equal to the values listed in Table 6.2.1.2 (annualized MLC) in the ASHRAE standard. It also is important to note that both the design and annualized MLC values are tied to the ASHRAE climate zones. When energy use is calculated using simulation techniques, it becomes obvious that the energy used has a direct correlation to the climate zone, primarily due to the ability to extend economization strategies for longer periods of time throughout the year. If we compare calculated annualized MLC values for data centers with the MLC values in ASHRAE 90.4, the ASHRAE requirements are relatively flat when plotted across the climate zones. This means the calculated MLC values in this example have energy-use efficiencies that are in excess of the minimum required by the standard (see Figure 7). 

Annual MLC=[cooling design energy (kWh)+pump design energy (kWh)+heat rejection design fan energy (kWh)+air handler unit design fan energy (kWh)]÷data center design ITE energy (kWh)


<< First < Previous Page 1 Page 2 Next > Last >>

Product of the Year
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
40 Under Forty: Get Recognized
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
MEP Giants Program
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
September 2018
Power boiler control, Product of the Year, power generation,and integration and interoperability
August 2018
MEP Giants, lighting designs, circuit protection, ventilation systems, and more
July 2018
Integrating electrical and HVAC systems, emerging trends in fire, life safety, ASHRAE 90.4
Data Centers: Impacts of Climate and Cooling Technology
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
Safety First: Arc Flash 101
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
Critical Power: Hospital Electrical Systems
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Data Center Design
Data centers, data closets, edge and cloud computing, co-location facilities, and similar topics are among the fastest-changing in the industry.
click me