Understanding control valve bench set

02/01/1999


C ontrol valves are frequently reused, disassembled for maintenance, or 'stroke tested' before installation. A key factor to ensuring that control valves perform as expected, is understanding how operating conditions, changes in packing material, spring compression, and other influences contribute to overall control valve performance.

During control valve and actuator sizing, several factors must be considered to ensure the actuator can move and maintain the valve plug in place while operating at process conditions.

Factors influencing control valve performance under operating conditions include:

  • Diaphragm loading pressure , which is frequently 3-15 psi, but may be significantly higher, especially when a positioner is being used.

 

  • Diaphragm effective area is defined by the size of the actuator. Most manufacturers offer a variety of actuator sizes.

 

  • Valve plug stroke and travel is determined by sizing the valve body to meet flow requirements.

 

  • Secondary forces acting on the valve plug in order of importance include static unbalance, dynamic unbalance, packing friction, stem size, and diaphragm hysteresis.

 

  • Spring characteristics are the most active of all influences and should be determined after all other factors have been considered.

A control valve and actuator assembly is tested on a bench, not under actual operating conditions. To meet leakage criteria, the actuator must be assembled to provide seating force beyond that required to stroke the valves fully open (or closed). Bench set consist of considering all the factors and forces, selecting a spring with the correct spring rate, and setting an initial compression on the spring. The result is a control-valve assembly that responds differently when tested on the bench, than when it is installed in the process where all active forces are in effect.

Before reusing a control valve in a different application, mixing and matching valves and actuators, adding or removing a positioner, changing components that influence hysteresis, or adjusting spring compression, it is best to discuss the planned changes with the original valve manufacturer.



Comments?
E-mail dharrold@cahners.com





Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me