The Need for Steam

As is the case with many health-care institutions, Kaiser Hospital in Sunnyside, Ore., periodically requires large amounts of steam for heating and sterilization. However, in the past, the difficulty was that one boiler was not sufficient to handle the sudden load swing. "In the wintertime, our two 300-hp fire-tube boilers would not hold the load, so we'd have to run our 500-hp boiler with a 30...

01/01/1970


As is the case with many health-care institutions, Kaiser Hospital in Sunnyside, Ore., periodically requires large amounts of steam for heating and sterilization. However, in the past, the difficulty was that one boiler was not sufficient to handle the sudden load swing.

"In the wintertime, our two 300-hp fire-tube boilers would not hold the load, so we'd have to run our 500-hp boiler with a 300 hp in standby, staying warm. And, in the summertime, we had one 300 hp on-line with the other 300-hp fire-tube in standby," explains Kaiser's Maintenance Manager Wayne Daggett.

Once GVA Northwest, LLC, was brought in as a consultant, the Portland, Ore.-based M/E firm informed the hospital that boiler size was not the problem. The real issue was that it took the standby boiler up to a half an hour to kick into full gear to meet sudden increases in the hospital's steam needs.

The solution was to retrofit with two 200-hp water-tube boilers, that had the ability to produce steam within minutes of being fired up.

With significantly higher efficiencies, the hospital has been able to meet its heat and steam needs with just one 200-hp boiler in the summer. In the winter, the entire load is also covered by a single 200-hp boiler on-line, but backed with the second boiler.

"The boilers run as needed, modulating themselves as the load dictates," says Daggett. "The increase in efficiency is really helping us out."

Looking at the numbers, GVA designer John Hilton confirms, "If you figure that previously, 600 to 800 hp was required for peak demand and now it's just 400, it is not surprising that the hospital estimates they are saving 25% on their fuel bill."





Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me