Intrinsic safety protects your plant against explosions

07/01/1997


Explosions can be prevented by limiting the amount of electrical energy available in hazardous areas or by containing the situation using bulky, heavy devices called 'explosion-proof enclosures.' Limiting excess electrical parameters such as voltage and amperage (current) requires the use of energy-limiting devices known as 'intrinsically safe (IS) barriers.'

Explosion-proof enclosures prevent or control explosive situations with brute force. They are heavy containers designed to hold an explosion inside. Electrical devices within explosion-proof enclosures can operate at normal power levels. Even under fault conditions, an explosion or fire may not occur because there simply isn't enough air within the sealed container to support combustion. If an explosion happens, the housings are strong enough to contain it.

Intrinsically safe barriers are more elegant. They limit the levels of power available in the protected area. If a spark or excess electrical heat cannot occur, neither can a fire or explosion. IS barriers eliminate the bulky enclosures, the use of conduit and expensive enclosure/conduit seals, and the associated installation costs.

Implementing intrinsic safety
While most users in Europe have used IS for many years, IS wasn't adopted as a part of the U.S. National Electrical Code until 1990 (Section 504). Implementing IS requires more intimate knowledge, and careful selection, of the devices involved than specifying explosion-proof enclosures. The need to perform many calculations to implement IS has turned off many engineers.

Three components comprise an intrinsically safe circuit: the target device, the intrinsically safe barrier, and the wiring.

Devices within the protected area are either simple (RTDs, LEDs, contacts, thermocouples, resistors, etc.) or complex (transmitters, solenoids, relays, transducers, etc.). Complex devices may store excess energy, and thus should be certified 'intrinsically safe' by a third party, such as Underwriters Laboratories (Northbrook, Ill.), Canadian Standards Assn. (Rexdale, Ontario, Canada), FactoryMutual (Norwood, Mass.), etc.

The simplest form of intrinsic safety barrier employs a resistor to limit current, at least two Zener diodes to limit voltage, and a fuse. The resistor limits the current to a specific value known as the short-circuit current. The Zener diodes limit the voltage to a value referred to as the open circuit voltage. The fuse will blow when the diode conducts. This interrupts the circuit, preventing the diode from burning, which could allow excess voltage to reach the hazardous area. There are always at least two Zener diodes in parallel in each intrinsically safe barrier. If one diode fails, the other acts as a backup providing safe operation and complete protection.

Selection of the proper intrinsic safety barrier requires calculating the open-circuit voltage and the short-circuit current. For complex devices, its necessary to also calculate the allowed capacitance value and the allowed inductance value. Results are then compared to 'ignition curves.'

Because different materials can be ignited by different levels of energy, Ignition Curves have been calculated for a wide variety of materials and can be obtained as Standards 3610 and 3611 from Factory Mutual, 1151 Boston-Providence Tpke., Norwood, MA 02062; Tel: 617/762-4300, Fax: 617/762-9375, or www.factorymutual.com.

The weak link
Intrinsic safety can be compromised at some point in time after the initial commissioning. This usually happens when an unrelated failure prompts improper maintenance or repair of wiring. Sometimes, to get things back up and running after a shutdown, temporary shortcuts are used. Left in place, these shortcuts can render intrinsic safety designs useless. Unfortunately, the effect of these shortcuts sometimes goes unrecognized--until its too late.

It's essential that good wiring documentation be created at installation, and that all future changes be noted as implemented to ensure intrinsic safety protection remains intact after repair.

Hazardous locations
DIVISION 1
(Continuous hazard and intermittent hazard)
Class I
Group ATypical example: Acetylene
Group BTypical example: Hydrogen
Group CTypical example: Ethylene
Group DTypical example: Propane
Class II
Group ETypical example: Metal dust
Group FTypical example: Coal dust
Group GTypical example: Grain dust
Class III
DIVISION 2





Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me