Cover story: Energy-Efficient Electric Motors

How to get the most out of energy-efficient motors: You have to do more than just look at the motor nameplate to get maximum energy savings. Are you ready for Dec. 19, 2010, the next major U.S. motor efficiency compliance deadline? Those truly interested in increasing efficiency will take a holistic view of overall machine design. Here's how to get inside motor efficiency to maximize savings.

11/15/2010


Control Engineering November 2011 coverConcern for the environment may motivate private individuals and the general public, but it’s a poor reason for making business decisions. Companies buying and installing electric motors have a far better business reason for trying to save electricity— making their operations more cost-efficient. In a rare confluence of factors, reducing electricity usage by installing more energy-efficient electric motors promotes both of these goals. And, it might be a requirement as of Dec. 19, 2010, the next major U.S. motor efficiency compliance deadline.

When one talks about high-efficiency motors, it is important to note that this term really refers to traditionally architected electric motors consisting of armature and field windings. “Induction motors are available in standard-, high- and premium-efficiency models,” said David Hansen, global product manager, Kinetix Motion Control, Rockwell Automation, “whereas permanent magnet motors are not.”

Graphic shows how higher efficiency motors save money. Source:   Baldor and Control EngineeringThe reason is that the permanent-magnet electric motor architecture is inherently more efficient, since no power is used to establish the stator magnetic field. John Malinowski, senior product manager - ac motors, Baldor Electric Company, pointed out: “ac induction motors have a family of motors that comply with NEMA Premium Efficiency per NEMA MG 1, tables 12-12 and 12-13, and IEC 60034- 30 [standards] for IE3 efficiency.”

For that reason, we limited this discussion to induction motors having stator coils wound on ferromagnetic cores, and save looking at the energy-efficiency characteristics of permanent magnet motors for a later discussion.

“Premium motors,” Malinowski continued, “are built to closer tolerances than older motors, run cooler, have less vibration, are quieter, and last longer.”

Control Engineering graphic shows how higher efficiency motors  save money. Source: Baldor and Control EngineeringHowever, “high efficiency in today’s ac induction motors,” said Peter Fischbach, industry sector manager, Bosch Rexroth Corp., “is achieved by improving the energy conversion paths and physical properties with new slot and winding geometries, advanced magnet and core materials, and the use of copper rotors for ac induction motors.”

What makes a motor efficient?

“The key to higher efficiency is reducing losses,” Malinowski said. “More copper in the winding to reduce stator losses, and higher-grade electrical steel reduces iron-core losses. Lower losses mean fewer watts to cool so smaller fans can be used, [further] reducing losses.”

Fischbach added: “The majority of the losses are caused by conductive losses in the stator and rotor and core losses, also called iron or hysteric losses.”

Hansen listed a number of design features that give these motors their high efficien

  • Winding Resistance—As winding resistance increases, efficiency decreases. To maximize motor efficiency, motor designers minimize resistance by maximizing slot fill (amount of copper windings in the stator slots) and minimizing end-turn radius (amount of copper windings outside the stator slots).
  • Lamination Material—Core losses are directly influenced by the material properties and quality of the steel used in the stator laminations. In addition, thinner laminations will lead to lower core losses in the stator than thicker laminations.
  • Lamination Tooth Geometry—Lamination tooth geometry impacts concentration of the magnetic flux inside the motor. Geometries that provide higher magnetic flux concentration will have lower stray losses and therefore higher efficiency.

It’s the system that counts

“The goal in most factory automation and industrial applications,” Fischbach suggesteded, “is efficient use of energy with the highest productivity. Therefore it is essential to analyze, model, and optimize the complete system before investing in individual components, like new motors.”

Table shows details of European motor efficiency deadlines. Source Lenze and Control EngineeringMalinowski agreed: “Better motors are easy to do as drop-in replacements [for less efficient units] but efficiency gains are limited. Using a 95% efficient motor is good but not when connected to a double-reduction [geartrain] that is 50% to 60% efficient, when a helical or bevel speed reducer may be 90% to 95% efficient.”

Fischbach also concurred: “Higher efficiency is a relative term there since we also have to consider other factors [that] affect the overall system efficiency, like cycle time or product output. For example, a direct drive torque motor with 80% efficiency could save more energy than a 95% efficient servo motor by eliminating inefficient drive train elements like gear boxes—and significantly increase production, too.”

What not to do

“The biggest mistakes,” Fischbach warned, “are made by engineers just focusing on the name plate efficiency of the motor, and expecting similar percentage energy savings in their specific application.

Different motors have different characteristics, which have to be matched to the application to benefit from the investment in a higher efficiency motor. For example, a more expensive premium efficiency ac induction motor will not save much energy if it’s run at partial load or idling for long periods of time.”

Malinowski provided the example of replacing a much older motor with a new premium motor on a centrifugal pump. The impeller would have been sized for the old motor’s speed. However, the new, more efficient, motor likely will run faster under the same load, leading to more overall power use. The system might be more energy-efficient, but the additional work it does may not provide any benefit.

“Designers who are truly interested in increasing efficiency,” advised Hansen, “will not simply look to replace a motor, but will take a holistic view of the overall machine design. Even a perfectly efficient motor, if connected to a poorly designed mechanical system, will not produce significant benefits with respect to energy savings. Any mechanical power transmission device between the motor and the load will have inherent inefficiency. The highest precision helical planetary gear heads, brand new out of the box, are at best 90% to 95% efficient. Worm gear boxes can be as little as 50% to 60% efficient.”

“The ultimate solution in terms of machine efficiency,” he concluded, “would be to eliminate the mechanical power transmission devices altogether through the use of direct drive permanent magnet servo motors.”

Do you buy or specify energy-efficient motors? How does the Dec. 19 motor efficiency deadline affect you? Take the Control Engineering Energy-Efficient Motors Survey, and share advice, as the Dec. 19, 2010, compliance deadline for the U.S. Energy Independence and Security Act of 2007 (EISA) approaches.

Other resources:

NEMA HE motor standard: www.nema.org/stds/mg1.cfm 

IEC HE motor standard: http://bit.ly/aHxTy6

U.S. Department of Energy, Energy Efficiency & Renewable Energy, Industrial Technologies www.eere.energy.gov/industry/

www.baldor.com/products/ ac_motors.asp

www.boschrexroth-us.com

www.lenzeamericas.com

www.rockwellautomation.com.au

More energy efficient motor reading

High-inertia servomotors for high, variable loads - Siemens Industry Inc. 1FK7 servomotor provides highly robust control response suitable for high- and variable-load inertia applications, such as feed and auxiliary axes on machine tools, and winders and unwinders on converting, packaging and printing equipment.

Severe duty motors deliver operational performance, lower GHG emissions - GE Energy X$D Ultra 841 IEC extra severe duty motors deliver operational performance and lower GHG emissions, the company said.

Brushless PM Torque Motors - Electric motors come in a rich variety of configurations to suit different purposes. One specialty motor type—known as a direct-drive, permanent-magnet (PM) torque motor—is characterized by a large diameter-to-length ratio and large number of magnetic poles to optimize torque production.



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Exploring fire pumps and systems; Lighting energy codes; Salary survey; Changes to NFPA 20
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me