Code requirements for arc flash reduction

NEC 240.87 is an important leap in arc flash safety for the electrical industry. This is a recap of an Eaton-sponsored webcast on April 24, which highlighted the 2014 standard.

04/24/2014


Arc flash incidents occur all too often and can impact many lives. To address this problem in the industry, electrical engineers turn to codes and standards. In a 10-year study of 120,000 workers, there were 125 injuries, as a result of arc flash, per year. Seventy-seven percent of these injuries were due to electrical arc, and 21% of these injuries resulted in permanent disabilities, according to speaker Jim Dollard, safety coordinator, IBEW Local 98. These statistics, Dollard said, demonstrate the importance of preventing and protecting one's employees from arc flash.

During the April 24 presentation, Dollard, who originally proposed NEC Section 240.7, shared his vision of workplace safety and the National Electric Code (NEC). He explained how Section 240.87 is paramount to those who work in and around electrical equipment. “In 2014 we have tremendous clarity,” he said in regards to the now more protective and proactive code standards.

The new code requirements for NEC 2014 Section 240.87 state: 

  • Documentation. Documentation shall be available to those authorized to design install, operate, or inspect the installation as to the location of the circuit breaker(s).
  • Method to Reduce Clearing Time. One of the following or approved equivalent means shall be provided:

    1. Zone-selective interlocking
    2. Differential relaying or
    3. Energy-reducing maintenance switching with local status indicator or
    4. Energy-reducing active arc flash mitigation system or
    5. An approved equivalent means.

In addition to Dollard, speaker Thomas Domitrovich, PE, LEED AP, Eaton, presented various arc reduction technologies and their appropriate application selection criteria. Speaker Ken White, a retired electrical engineer, Olin Chlor-Alaki, recounted a personal experience with a near arc flash disaster and how technology played an important role in maintaining safety in his facility.

View the full, on-demand hour-long Webcast and extended Q&A in early May. You can also join the discussion about this webcast on Twitter at #CSEarcreduction.

The Webcast speakers were Thomas Domitrovich, PE, LEED AP, Eaton, Pittsburgh; Ken White, retired, Olin Chlor-Alaki, Niagara Falls, N.Y.; and Jim Dollard, safety coordinator, IBEW Local 98, Philadelphia. The Webcast moderator was Jack Smith, content specialist, CFE Media.

- Edited by Jessica DuBois-Maahs, associate content manager, CFE Media.



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me