Carbon-Neutral Energy Solutions Laboratory

New Construction; Carbon-Neutral Energy Solutions Laboratory; HDR Architecture Inc.

08/15/2013


The building is intended to act as a prototype living, learning laboratory and demonstrate its passive and active approach to energy efficiency. Courtesy: HDR Architecture Inc.; Jonathan HillyerEngineering firm: HDR Architecture Inc.
2013 MEP Giants rank:
6
Project:
Carbon-Neutral Energy Solutions Laboratory
Address:
Atlanta, Ga., United States
Building type:
Research/lab/high-tech
Project type:
New construction
Engineering services:
Automation & Controls, Code Compliance, Electrical/Power, Fire & Life Safety, HVAC, Lighting
Project timeline:
November 2008 to August 2012
Engineering services budget: $378,000
MEP budget: $11 million

Challenges

The Georgia Tech Carbon-Neutral Energy Solutions (CNES) Laboratory Photovoltaic panels are located on the roof, south wall, south canopy, and parking lot canopies. Courtesy: HDR Architecture Inc.; Jonathan Hillyerbegan as a flexible, design-build, high-bay laboratory. Located across the railroad tracks from the Georgia Tech campus, on its NARA Science Park site, it would be a low-tech, shop-like laboratory—flexible enough to be usable, even without a clearly defined user. Taking advantage of the building's low-tech qualities and the site's lack of pretentiousness, Georgia Tech decided to shift gears and steered the team (Georgia Tech, Gilbane, and HDR) to focus on the carbon-neutral lab, with specific instruction to follow a rational design process. The project would be a model. The research would explore carbon-neutral energy solutions, hence the name. The building would highlight three types of flexible laboratory spaces: high-bay (for large-scale research), mid-bay (for lower-scale projects requiring more stringent environmental control), and computation laboratories.

HDR began with a healthy respect for the energy demands of modern laboratory environments and a sense that this low-tech lab might somehow be different—a simple structure with only necessary systems. The firm started with the idea of passive design first: pay attention to climate and The design adheres to the core principles of the facility's sustainable mission, simply and directly. The south elevation shaded glazing system maximizes daylight and views with minimal solar heat gain. It also incorporates crystalline photovoltaic panels to generate renewable energy. Courtesy: HDR Architecture Inc.; Jonathan Hillyer orientation; maximize daylight and natural ventilation. HDR worked with EMO, its energy modeler, to establish a baseline energy model, which told the firm what to attack. Goals beyond energy efficiency were established. There would be no lights during the day and no potable water for irrigation. The firm would minimize plug loads, limit the number of materials by letting the structure be the finish, and maximize renewable energy..

Solutions

Passive design: First, the team was challenged to develop a new, innovative prototype that would enable breakthrough research initiatives, educate students, and demonstrate innovative energy-saving features. The team strived to reduce energy demand by developing and testing passive-design concepts; studying contemporary carbon-neutral buildings; establishing a working definition of net-zero site-energy use; incorporating baseline energy-modeling; and challenging conventionally held environmental requirements. Energy modeling was used to evaluate energy-savings strategies and to help determine which systems would be incorporated into the design. The mission of Georgia Tech's new 42,000-sq-ft Carbon-Neutral Energy Solutions laboratory is twofold: first, to support Georgia Tech's Strategic Energy Institute; and second, to continue Georgia Tech's leadership in sustainability. It is a center for research in carbon-neutral energy conversion technologies located in the heart of Atlanta. Courtesy: HDR Architecture Inc.; Jonathan HillyerThe design team collaborated with Georgia Tech to develop design concepts, including a matrix of energy-savings options, and evaluate first costs, lifecycle costs, and carbon savings for each. A cost-benefit analysis of various design options encouraged low-cost, high-benefit solutions, such as forced natural ventilation in the high-bay and reduced night time operations. High-cost, low-benefit solutions—such as translucent panels insulated with nanogel—were discouraged.

Program: Three space typologies CNES offers include process-intensive research and industrial-scale infrastructure capability to support a varied range of project-based research. The facility has been planned to provide space that can be quickly modified both functionally and environmentally for maximum flexibility. The supply and distribution systems for liquid and This view from across the tracks captures the differentiation between the open, translucent high-bay lab and the solid, enclosed specialty combustion labs. Courtesy: HDR Architecture Inc.; Jonathan Hillyergaseous materials have been planned to accommodate future exterior bulk storage areas that will tie into the building. These systems have been evaluated to ensure that future programs will function in the safest conditions possible. The building has been broken into three space types, organized to accommodate evolving research programs; minimizing the need for modifications for different research programs; and allowing projects to be easily moved in and out: 1. high-bay, 2. mid-bay, and 3. computational labs. Breaking the program into three types allows for maximum flexibility, especially between high- and mid-bay laboratories. It also gave the team a way to evaluate each space type and design each independently. The high-bay laboratory was designed with a temperature range of 68 to 80 F, anticipating that heavier work can adapt to that range. The mid-bay lab was designed with a 70 to 76 F range with the ability to more stringently control temperature and humidity for individual labs. The computational labs were also designed to a 70 to 76 F temperature range, which is an atypical adaptation of a traditional office environment.

Utility infrastructure: The mid- and high-bay spaces are separated by a shared utility zone, for easily reconfigurable utility distribution. This central spine is designed to provide the needed utilities within each space without compromising the mobility of the equipment. Within the high-bay, accessible utility trenches in the slab run north-south and along the north wall, allowing unobstructed operation of the industrial crane. In the mid-bay, all utilities are routed overhead, allowing the free configuration of lab benches below. A catwalk above the utility zone is accessible from the second level, where the computational labs and offices are located. The loading dock adjacent to the utility zone allows equipment and supplies to easily be brought into the building as well as directly into the high-bay space.

Georgia Tech hopes that visitors and students will go back to their communities and help reduce our societal carbon footprint by utilizing similar strategies to those incorporated in its Carbon-Neutral Energy Solutions Laboratory. Courtesy: HDR Architecture Inc.; 2013 Jonathan HillyerThe high-bay shop-like, flexible, project-based laboratory accommodates industrial scale-fabrication experiments. Courtesy: HDR Architecture Inc.; 2013 Jonathan Hillyer

The high-bay and mid-bay laboratories are located on the ground floor separated by a shared utility zone. Transparent garage-type doors allow the movement of large equipment in and out of the mid-bay. Courtesy: HDR Architecture Inc.The computational labs and offices, as well as meeting areas for collaborative work, are located above the mid-bay lab, with unobstructed views into the high-bay lab. Courtesy: HDR Architecture Inc.

The section describes building mechanical and utility distribution strategies. Courtesy: HDR Architecture Inc.



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
How to use IPD; 2017 Commissioning Giants; CFDs and harmonic mitigation; Eight steps to determine plumbing system requirements
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me