Kaleida Health, Clinical, Medical Research Building
New construction: Kaleida Health, Clinical and Medical Research Building; Cannon Design
Project name: Kaleida Health, Clinical and Medical Research Building
Location: Buffalo, N.Y.
Firm name: Cannon Design
Project type, building type: New construction, hospital
Project duration: 4 years
Project completion date: June 1, 2012
Project budget for mechanical, electrical, plumbing, fire protection engineering only: $69.5 million
Engineering challenges
Kaleida Health, Clinical and Medical Research Building: Gates Vascular Institute (GVI), and UB Clinical Translational Research Center/Incubator (CTRC) Challenge: Create a hospital and translational research center with “100-year” flexibility. The GVI is a one-of-a-kind facility planned as the cornerstone of a world-class academic medical center being developed by Kaleida Health and the University at Buffalo, Buffalo 2020 Development Corporation. The $291 million, 476,000-sq-ft, 10-story facility consolidates services previously performed at two separate facilities, including cardiac catheterization, neurovascular intervention, electrophysiology, peripheral vascular intervention, cardiac surgery, neurosurgery, and peripheral vascular surgery—and provides the region with a major heart and vascular center. There is also an entire medical research facility with laboratories, imaging, a vivarium, and a research incubator.
Solutions
To maximize flexibility and create a “100-year building,” the facilities” structure and its engineering systems infrastructure is designed utilizing a Universal Grid, a 31-ft 6-in. x 31-ft 6-in. x 18-in. floor-to-floor structural system with “headered” mechanical and electrical systems distribution to accommodate future technologies in operating suites and conversion of building zones to entirely different functions without having to modify “head-end” mechanical, electrical, and plumbing systems.
The new facility is provided with steam, chilled water, electricity, and emergency power from an expanded central plant that serves the entire medical campus. We added 2,200 tons of chilled water capacity to the existing 3,700-ton chiller plant. Campus distribution loop systems were created for the steam and chilled water systems. The chiller plant is also being converted to a variable primary flow system with upgraded chiller optimization controls. Chilled water will be provided year-round, and a winter free-cooling heat exchanger was designed to provide up to 1,200 tons of winter free-cooling when outside air temperature is below 40 F. A 6-MW emergency generator plant is being constructed to provide full backup power for the new facility. The electrical systems’ design also included the phased upgrade of all primary electrical distribution serving the existing hospital to accommodate capacity for the new building, including expanding the 23 kV substation and replacing the secondary 5kV distribution switchgear and underground feeder ductbank relocations required to clear the area for the new building. Coordination meetings were held with National Grid Engineers to plan the physical expansion of the substation, including construction phasing, ductbank and feeder arrangements, and equipment selection and layout. Design work included protective relaying equipment, three-line diagrams, a coordination study, and short-circuit calculations.
Do you have experience and expertise with the topics mentioned in this content? You should consider contributing to our WTWH Media editorial team and getting the recognition you and your company deserve. Click here to start this process.