Using HVAC and lighting demand response

Strategies for handling DR fall into two basic categories: standby generation and load curtailment.

03/11/2013


 

Figure 2: HVAC DR requires recovery time, which may affect occupant comfort and decrease productivity. Courtesy: Lutron Electronics

Part I of our series on demand response (DR) strategies, introduced the goal of a commercial DR strategy. This article discusses how strategies for handling DR fall into two basic categories: standby generation and load curtailment (also known as load shed). Let's start with a discussion about load curtailment. According to a 2003 Dept. of Energy (DOE) survey, lighting and HVAC together account for two-thirds of the electrical power usage in a typical office building. That is good news, since lighting and HVAC also are best suited to being controlled by a responsive and programmable DR system, and should be first and second on a list of curtailment strategies. 

Despite the fact that annually, lighting and HVAC electricity use is virtually equal, HVAC curtailment is often the only DR strategy used in a building. Theoretically, this makes perfect sense since demand peaks are usually associated with outside climate conditions that closely mirror the HVAC demand. In other words, the warmer the outside air temperature, the more electricity it takes to cool the building—and the cooler the outside temperature, the more electricity it takes to heat the building. Therefore, during peak demand HVAC typically accounts for the larger share of power usage. 

This leads back to the risk-reward proposition that a faster reaction time equals greater reward. HVAC accounts for the larger share in a demand event, but with that come multiple DR management considerations including predictability and responsiveness. HVAC is weather-dependent, so predictability is limited. After all, it is difficult to predict how cold or warm it will be next April 3. And HVAC has to manage the relationship between three variables: temperature, ventilation, and humidity. HVAC does not respond either immediately or proportionately when you change settings. The thermal mass of the building is highly complex and has tremendous momentum: There is an extensive lag time between a change to the HVAC setting and the desired result. Reversing HVAC is like trying to reverse a moving train—it's a gradual process. HVAC also has a recovery time to account for. Radical adjustments can produce unintended peaks, which may be worse than no load shed at all. 

Figure 3: Lighting DR requires no recovery time and results in very little change to occupant comfort or productivity during the demand event.

Lighting control: Linear, responsive DR strategy

So what about lighting? As we mentioned before, lighting and HVAC are almost equal in yearly power usage, but lighting use is not climate driven. Day-to-day, lighting is essentially constant, much the same at 9 a.m. as it is at 3 p.m. with only slight deviations as a result of daylight harvesting. Even with daylight harvesting, algorithms can effectively calculate and account for the angle and arc of the sun in respect to a building's exact location, making lighting levels even more predictive. As opposed to HVAC, lighting is linear and highly responsive. Lighting power is simply the product of voltage and current, and since the voltage is steady there is only one variable—current. Reduce current and lights go down; increase current and lights go up. The speed at which you take current away or put it back is the speed at which the lights change, making lighting easier to manage than HVAC. It is the predictive nature of lighting along with its linear response that make it such a useful demand strategy, especially as a means of quickly contributing to response levels that HVAC can achieve only over time. 

Occupant productivity is always an issue with demand events (see Figures 2 and 3). This is probably the biggest reason on-site generation is used more than curtailment. On-site generation consumes resources and contributes to faster equipment degradation but will not negatively impact productivity. Lighting, on the other hand, works in conjunction with the marvelous, innate qualities of the human eye. The pupil naturally expands to counter a decrease in light. A study by the Lighting Research Center, Rensselaer Polytechnic Institute, has shown that most occupants will not detect a gradual change in light level such as a 15%-20% decrease in light output. Gradual, slow, and steady changes over a few seconds are offset by the eyes’ natural capabilities and will have no impact on productivity. Part III of our series will cover federal and local legislation, and the future of DR.


Scott Ziegenfus is a senior applications engineer with Lutron Electronics Co. Inc. Ziegenfus has an electrical engineering degree from Lafayette College. He is an educational programs chair and board member for the Delaware Valley Chapter of the U.S. Green Building Council and is a certified LEED Study Guide Facilitator. Ziegenfus also serves on ASHRAE standards committees SPC 201P–Facility Smart Grid Information Model and SSPC 135–BACnet.



RANDALL , OH, United States, 03/14/13 11:10 AM:

The issue of lighting impact is well stated, but the HVAC approach does not consider the "entire" SYSTEM impact.
By lowering the site relative humidity, it is possible to increase space temperature significantly with ZERO impact on occupant comfort. 80 degrees F at 35% RH has the same "feel" as 73 and 50% RH- But it cuts the thermal gain of the space (at peak) by 32% while raising the ambient temperature the causes thermal transfer, reducing the hours of heat gain- both of which lower the cooling load of the space- cutting cooling energy use and required supply air volume (often by about 15%). The higher room temp also cuts the supply air volume by 32% (25 vs 18 degrees deltaT). As a result- supply air volume needs are cut about 38%. The fan only needs to supply- at peak load- 62% of the original air volume. That will result in a "constant" fan energy usage of only 24% of the original load and cooling load energy savings of 15% of original load WITHOUT causing ANY discomfort to the occupants.
The lower air volume will allow the existing coils to make cooler air which will yield a dryer space so the "upgrade" can be done at minimal expense- if a VFD drive is needed. Maybe the CHW temp will need to be lowered a couple of degrees but there is no cost in that action.
As noted, the cooling load (and energy use) will be cut by about 15% and the fan energy will be cut by 76%- likely better than what might be achieved with some form of temp reset and no occupant complaints.
RANDALL , OH, United States, 03/14/13 11:20 AM:

Another- better- option to cutting demand is to use a high efficiency CoGeneration system, coupled with a thermally-driven cooling system, to eliminate on-site "outside" electrical energy use. Such an approach will cut operating costs AND help "save the world" by cutting environmental releases (CO2 and NOx) by 70% or more- depending on the amount of displaced power. Additionally, if the CoGen system is able to burn bio-fuels, there is an added benefit in further cutting "normal"- non-renewable hydrocarbon energy use. Obviously, when cooling is NOT needed the heat can support site heating loads.
Additionally, the waste heat from the cooling system can be "cultivated" to preheat "hot water" to further lower thermal demand AND cut tower water use because of the reduced thermal reject load.
SIVA , AL, India, 03/24/13 12:23 PM:

a very good article. temperature graph is excellent
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
integrated building networks, NFPA 99, recover waste heat, chilled water systems, Internet of Things, BAS controls
40 Under 40; Performance-based design; Clean agent fire suppression; NFPA 92; Future of commissioning; Successful project management principles
BIM coordination; MEP projects; NFPA 13; Data center Q&A; Networked lighting controls; 2017 Product of the Year finalists
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me