Trends In Major Power Distribution In Large Data Centers, the Rebirth of the 'Loadcenter' Unit Substation Concept

This series of "Cut the Copper" blogs is in direct response to questions I’ve received from many young engineers on the staffs of various data center owners and their consulting engineering firms I’ve recently met.

04/04/2012



You should know before we begin that I’m a highly opinionated old guy who’s been around the electrical industry for a very long time. What I’ll be writing will likely trigger controversy—the story will be light on theory, and heavy on practical experience. I expect to see agreement from about half the electrical industry, and strong disagreement and some hate mail from the other half. But, in any case, you might agree that the history is interesting, so let’s begin the story with some background.

Liquid-Filled Medium Voltage Distribution Transformers and “Loadcenters”

For the first 35 years of the U.S. electrical industry, everyone could see that the good old mineral oil filled distribution transformer was a wonderful apparatus—except when it failed catastrophically with a ruptured tank and a good supply of oxygen and an ignition source—in which case it became a lethal ball of hot, orange flames and dense black smoke. To be installed safely indoors, oil-filled transformers had to be placed only inside enclosed fireproof vaults. 

That all changed in 1935 when Monsanto Chemical Co. acquired a small chemical company named Swann Chemical Co., who had developed a new electrical insulating fluid compound having the name “Askarel.” The liquid had all of the desirable properties of mineral oil for use as an insulating fluid in transformers, including high dielectric strength, good thermal conductivity, and low coefficient of expansion. But, beyond that, it was an inert, synthetic chemical product that could hardly be ignited under any circumstances—its chief benefit was that it was essentially non-flammable, in addition to possessing all the other good properties you’d want in a transformer insulating fluid. 

Monsanto began to market the product to the electrical industry under the trade name Aroclor. The electrical industry giants back in the day, GE and Westinghouse, immediately recognized the potential of this new liquid, and began purchasing it for use in capacitors, transformers, lighting ballasts, and other products. GE marketed the product under the trade name Pyranol, and Westinghouse marketed the product under the trade name Inerteen. The new products containing those liquids were hugely successful and much appreciated in their respective markets.



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
BIM coordination; MEP projects; NFPA 13; Data center Q&A; Networked lighting controls; 2017 Product of the Year finalists
Emergency lighting; NFPA 3 and 4; Integrated building systems; Smart lighting, HVAC design
Designing for energy efficiency; Understanding and applying NFPA 101 for mission critical facilities; Integrating commissioning and testing for fire alarm systems; Optimizing unitary pumping solutions
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
Driving motor efficiency; Preventing Arc Flash in mission critical facilities; Integrating alternative power and existing electrical systems
Putting COPS into context; Designing medium-voltage electrical systems; Planning and designing resilient, efficient data centers; The nine steps of designing generator fuel systems
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
click me