Thermal Shock-Ready Heat Pumps on Georgia's Mind

When thermal shock rendered boilers at North Springs High School inefficient and ineffective, Joseph Clements, coordinator of utilities services for Fulton County schools in Georgia, knew it was time for a change. Low-temperature water entering the gas-fired boilers had caused sooting in the combustion chamber and serious cracks in the refractories.

03/01/2003


When thermal shock rendered boilers at North Springs High School inefficient and ineffective, Joseph Clements, coordinator of utilities services for Fulton County schools in Georgia, knew it was time for a change. Low-temperature water entering the gas-fired boilers had caused sooting in the combustion chamber and serious cracks in the refractories.

"The original boilers had been poorly applied," says Clements, referring to the fact that these boilers were not designed for low-temperature operation. Technically, there should have been a three-way valve redirect ringing the cooler water to prevent thermal shock on the boilers. However, by the time the school sought help, the boilers were beyond repair.

Water-source heat pumps

In the case of North Springs High, low return-water temperature was a product of the existing water-source heat pumps, which provide cooling in the summer and heat in the winter.

The boilers were connected to the heat pump loop, and water was drawn from the main building loop through the boiler using recirculation pumps. Heat pumps extract heat from the loop water, returning water at very low temperatures and causing thermal shock and condensing in the existing noncondensing boilers.

The goal of a retrofit was simple: employ a reliable and long-lasting replacement while avoiding expensive changes to the surrounding heating plant infrastructure.

Two high-efficiency 2-MBh boiler units were selected for the 250,000-sq.-ft. school. The stainless-steel, fire-tube design of the new boilers can withstand low return-water temperatures without degrading the heat exchanger over time.

And there were other benefits, as well. No changes or re-piping were required in the existing infrastructure. Also, since the new installation, gas usage has dropped. In fact, a comparison of energy consumption from 1998 to 2002—the year after the boilers were installed—shows that gas usage was almost cut in half during the major heating months.

With seamless 20:1 turndown, the equipment eliminates cycling losses in the two-unit installation. Offering up to 97% efficiency at part-load firing rates, the units are configured to operate at low-fire in parallel with each other.

One final attraction of the new equipment is that if one boiler is shut down, the other is able to maintain the typical heating load for the school's more than 1,600 students.





Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Boiler basics; 2017 Product of the Year winners; Manufacturing facilities Q&A; Building integration; Piping and pumping systems
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me