Selective coordination studies for mission critical environments

08/19/2013


Understanding the code 

To understand the full potential impacts of recent changes to the NEC, it is important to quote the new definition of “selective coordination” and the new codes in sections 100, 517, 700, and 701 as they apply to emergency and standby systems, which are a part of mission critical systems: 

NEC 100 definitions – coordination (selective): Localization of an overcurrent condition to restrict outages to the circuit or equipment effected, accomplished by the choice of overcurrent protective devices and their ratings and settings. 

NEC 517.26 - application of other articles: The essential electrical system shall meet the requirements of Article 700, except as amended by Article 517.

NEC 700.27 - coordination: Emergency system(s) overcurrent devices shall be selectively coordinated with all supply side overcurrent protective devices. 

NEC 701.18 - Coordination: Legally required standby system(s) overcurrent devices shall be selectively coordinated with all supply side overcurrent protective devices. 

For clarity, it is important to include the NEC definition (Section 100) of overcurrent and the fine-print notes defining emergency systems and legally required standby loads in Sections 700 and 701:

Overcurrent: Any current in excess of the rated current of the equipment or ampacity of the conductor. It may result from overload, short circuit, or ground fault. 

A “short circuit” is noted as one of the items that can cause an overcurrent. The typical molded case circuit breaker combination with the upstream breaker somewhat larger than the downstream breaker does not have a problem coordinating in the overload area of the time current curve, but a high level of current in the short circuit area of the time current curve can represent significant problems to selective coordination. 

NEC Section 700.1 “fine-print note” (FPN) No. 3: Emergency systems are generally installed in places of assembly where artificial illumination is required for safe exit and panic control… Emergency systems may also provide power for such functions as ventilation, fire detection and alarm systems, elevators, fire pumps, public safety communication, and industrial processes. 

NEC Section 701.2 FPN: Legally required standby systems are typically installed to serve loads, such as heating and refrigeration systems, communication systems, sewage disposal, lighting systems, and industrial processes, that, when stopped during any interruption of normal electrical supply, could create hazard or hamper rescue or fire fighter operations.

Arc flash studies 

We are seeing more requirements for arc flash studies for critical infrastructure. The amount of arc flash energy levels that can be produced at any point in an electrical distribution system depends on the amount of fault current that is available and the speed at which the overcurrent protective device operates. 

The arc flash calculation will determine the amount of thermal incident energy to which an electrician’s chest and face can be exposed to at working distances. This energy level is measured in Joules/cm2 or calories/ cm2

These calculations are provided to determine the amount of personal protective equipment (PPE) that is required to operate or maintain the equipment with exposed live parts. The flash boundary is the approach distance limit to the exposed live parts during maintenance, operation, or testing. If the electrician is not appropriately protected in this flash boundary, he could receive second-degree burns. 

Figure 3: This graph illustrates the ground fault setting for a 2,500 amp main breaker and the ground fault setting for a 400 amp sub breaker. There is clear separation between the ground fault curves. A ground fault on the 400 amp feeder would trip the 4Typically, a fault current study is first performed on a project. The second step is to perform a coordination study to determine the optimum settings of the overcurrent protective devices and protective relays to provide for as much selective coordination as possible. Then as a third step, after the settings of the breakers and relays are determined, the arc flash study is performed. Therefore, settings that provide the optimum separation between the time current curves and isolate a fault to the smallest area possible may actually cause higher levels of arc flash energy. 

NEC 517-17 requires that if ground fault protection is provided for the service disconnecting means, then an additional step of ground fault protection shall be provided in the next level of feeder disconnecting means downstream toward the load. Figure 3 is an example of a properly coordinated ground fault study.

Ground fault settings

NEC 230-95 indicates that all 480 V, 3-phase services 1,000 amps and over must be installed with a ground fault relay. The setting of the ground fault relay cannot exceed 1,200 amps, regardless of the size of the overcurrent protection device. In addition, the time delay cannot exceed 1 second (60 cycles) for ground fault currents of 3,000 amps or more. There shall be a minimum of 6 cycles (0.1 second) ground fault delay between ground fault devices in healthcare facilities. 

Ground fault settings for main breakers serving downstream motors that are set too low or too fast may trip a main overcurrent protection device before tripping the local thermal magnetic overcurrent protection device during motor starting ground faults. On the other hand, ground fault settings that are too high can cause undue damage before a ground fault is interrupted. It is important to provide the ground fault setting that will not permit nuisance tripping, but will protect the electrical equipment from excessive damage during an event. 

It has been my experience that sometimes perfect coordination between a set of devices cannot be obtained. Certain settings may be required on a breaker that could affect the settings of many breakers. In some cases, there may be many levels of breakers that cause overlap of the breaker curves within the tolerance of the curves. In these cases experience will help the engineer make judgment calls as to compromises in coordination between devices. The engineering behind providing protective coordination studies is not a perfect science. 

Often, completed projects have no protective device study. In such cases the breaker manufacturer will ship the breakers with all settings set to the most sensitive. This will ensure the most protection but will increase false trips and is typically not good for the reliability and uptime of the systems. As soon as the owner complains of a false trip, the facility personnel will probably set all of the dials to least sensitive. This will reduce false trips, but may not adequately protect the electrical system and reduce selective coordination of the system. 

A coordination study is typically required to ensure that the most reliable electrical system has been installed. In addition, there are instances where NEC requires that a study be performed. In either case, the cost of a coordination study is pretty cheap insurance for most installations that would be adversely affected by an extensive power outage.


Keith Lane is president and CEO of Lane Coburn & Assocs. He is a member of the Consulting-Specifying Engineer editorial advisory board, and was a 2008 40 Under 40 award winner. Lane has more than 20 years of experience designing, commissioning, and optimizing mission critical facilities


<< First < Previous 1 2 Next > Last >>

Eddy , Brittish Columbia, Singapore, 12/16/13 12:37 AM:

Dear Sir,
I would like to share on SPOF (Single Point of Failure)

Single Point Of Failure (SPOF) And Resiliency Report

Background

In engineering, redundancy is the duplication of critical components or functions of a system with the intention of increasing reliability of the system, usually in the case of a backup or fail-safe. Global Switch are contractually obliged to provide at least N (full duty capacity) + 1 but in many instances we actually exceed these requirements with N + N

This level of redundancy can sometimes, by virtue of design or construction deficiencies have single control or other functions which in the event of failure will cause the system in which they are installed to fail despite having redundancy in terms of base units. These are called “single points of failure” or SPOFs.

It is important that to maintain the required 100% uptime that these SPOFs are identified and that an educated decision be made as to whether it is acceptable to live with these SPOFs or whether it is required to maintain acceptable levels of reliability or an acceptable limitation of risk necessary to engineer these SPOFs out.

Systems can be made more robust by adding redundancy or duplicating the plant or device in all potential SPOFs thus removing the single point of failure.

General Objective

The assessment of a potential SPOF involves identifying the critical components of a complex system that would result in a total systems failure in should it malfunction. Highly reliable systems should not rely on any such individual component failure. Clearly it is not sufficient to identify the weakness on its own; a decision has to be made as to whether the risk as acceptable or not and to establish the cost and feasibility of engineering out this single point of failure by adding additional redundant services. Providing master/slave controllers is a typical example of this.

Approach

This process would entail an initial highly detailed desktop analysis covering both electrical and mechanical schematics’. Any single items of critical plant should be noted these should be at least double fed or be duplicated in terms of function elsewhere such that their failure would not impact the service delivery of the site. BMS systems, Pressurisation units and water filtration units on a sealed system plus monitoring systems of most types are just a few examples of such plant. Careful consideration would have to be made of each of the systems such as DRUPS, Chiller, Generators, UPS, CRAC units to ensure that they did not have any single shared function that could cause the environment to go out of control.

A physical survey would have to be carried out to identify such weaknesses of generator cables running over transformers. If the transformer explodes the resultant fire would damage the cables. Whilst this is not a true single point of failure it is a potential risk which affects the site resilience. The operating regime for each system will need to be considered to ensure there is nothing within the system that would pose a total system risk. A good example of this is an N + X redundant system where the modules feed through a single static switch or output board. These two items are then the single points of failure.




Potential area for SPOF:

1. HV distribution:
a. Locations of HV switch room.
b. Main incoming power feed cables routes to HV switch gear.
c. Locations of the HV transformers & supplying cables routes.
d. Radial or ring feed for the incomer within the building
e. Radial or ring feed for the incomer from utility provider.

2. LV distribution:
a. LV main switch board location
b. LV distribution routes from HT transformer

3. DC system:
a. Location of DC system
b. DC system supply cable routes

4. Stand-by power:
a. Gen-set location
b. Gen-set switch room location
c. Cable routes from gen-set to gen-set switch board
d. Generator outgoing cable routes to main LV boards
e. Gen-set starting devices (Electrical / pneumatic starter)
f. Location of Compressors & air dryer with air reservoir if pneumatic starter
g. Power supply for Compressors & ait dryer
h. Routes of air pipe to the pneumatic starter for gen-set from air reservoir.
i. Location of diesel storage tanks
j. Location of diesel transfer pumps
k. Power supply for diesel transfer pumps
l. Single or multiple pipe line for the following:

i. Suction pipe from diesel storage tanks
ii. Discharge pipes from pumps to gen-set day tank
iii. Return pipes to the diesel storage tanks from gen-set day tank
iv. Over flow pipes to the diesel storage tanks from gen-set day tank
m. Diesel pipes routes to the gen-set day tanks

5. UPS supply to IT loads:
a. Location of UPS room
b. UPS topology (Single or modular)
c. Static by-pass module topology for UPS
d. Cables routes to UPS from MSB
e. Cables routes to Static by-pass module from UPS
f. Cables routes to Static by-pass module from MSB
g. Location of Battery rooms
h. Battery configurations, No. of strings etc
j. Cable routes to UPS from Battery isolator (if the battery far away from the UPS)
k. UMSB locations
l. Cables routes to UMSB from UPS
m. Cables routes to UMSB from MSB (Maintenance by-pass feed)

6. STS
a. Location of STS
b. Cables routes to STS from UMSB (A feed)
c. Cables routes to STS from UMSB (B feed)


7. PDU
a. Location of PDU
b. Cables routes to PDU from STS (main feed)
c. Cables routes to PDU from UMSB (Maintenance by-pass feed)

8. RDU
a. Location of RDU
b. Cables routes to RDU from PDU

9. Final circuits
a. Location of cee-forms / industrial socket for Racks from A feed RDU
b. Location of cee-forms / industrial socket for Racks from B feed RDU
c. Cables routes for cee-forms / industrial socket from RDU A feed
d. Cables routes for cee-forms / industrial socket from RDU B feed

13. Other critical services:
a. Power supply Water detection
b. Power supply fire alarm panel
c. Power supply for VESDA
d. Power supply for security equipment’s (CCTV, CAC, PA system, AV system)
e. Security systems topology (single or hot-stand by)
f. Location of security system server
g. Lighting & small power DBs with ATS or MTS
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
40 Under 40; Performance-based design; Clean agent fire suppression; NFPA 92; Future of commissioning; Successful project management principles
BIM coordination; MEP projects; NFPA 13; Data center Q&A; Networked lighting controls; 2017 Product of the Year finalists
Emergency lighting; NFPA 3 and 4; Integrated building systems; Smart lighting, HVAC design
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
Driving motor efficiency; Preventing Arc Flash in mission critical facilities; Integrating alternative power and existing electrical systems
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me