Selective coordination in elevators

Selective coordination in elevators is required when more than one elevator is supplied by a common feeder.

08/19/2013


Figure 2: The graph indicates a 200 amp breaker in the main distribution gear feeding an elevator control panel with a 100 amp and a 70 amp fuse. The study must ensure that the two fuses will trip in a fault condition in any one of the separate elevator fSelective coordination is required when more than one elevator is supplied by a common feeder, per NEC Article 620-62. Figure 2 shows an example of a coordination study illustrating the feeder breaker overcurrent protection, the elevator fuse overcurrent protection, and the elevator motor start-up curves.

 


Keith Lane is president and CEO of Lane Coburn & Assocs. He is a member of the Consulting-Specifying Engineer editorial advisory board, and was a 2008 40 Under 40 award winner. Lane has more than 20 years of experience designing, commissioning, and optimizing mission critical facilities.

- See how selective coordination studies are used in mission critical environments below.



SIVA , AL, India, 09/08/13 03:31 AM:

excellent.

I suggest for independant supply from diffrent feeders with correct rating
DANIEL , GUANAJUATO, MEXICO, 09/26/13 08:34 PM:

This kaind of articles really help.

Thank You.
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Emergency lighting; NFPA 3 and 4; Integrated building systems; Smart lighting, HVAC design
Designing for energy efficiency; Understanding and applying NFPA 101 for mission critical facilities; Integrating commissioning and testing for fire alarm systems; Optimizing unitary pumping solutions
Economics of HVAC systems; NFPA 110-2016; Designing and choosing modular data centers
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
Driving motor efficiency; Preventing Arc Flash in mission critical facilities; Integrating alternative power and existing electrical systems
Putting COPS into context; Designing medium-voltage electrical systems; Planning and designing resilient, efficient data centers; The nine steps of designing generator fuel systems
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
click me