Selecting a chiller for life

The evaluation criteria used to select a chiller involve the owning costs and the operating costs. The owning costs include acquisition, installation, and replacement costs; salvage value; discount rate and financing method; and fixed or periodic costs such as insurance and property taxes. These costs are exclusive of costs associated with operating the chiller.

01/01/2008


The evaluation criteria used to select a chiller involve the owning costs and the operating costs. The owning costs include acquisition, installation, and replacement costs; salvage value; discount rate and financing method; and fixed or periodic costs such as insurance and property taxes. These costs are exclusive of costs associated with operating the chiller.

The performance characteristics of the selected equipment, its predicted useful service life, its hours of operation, and the loads applied, affect operating costs. Capital investment costs are firm and have an immediate effect on the project finances. Predictions of future costs and usage estimate operating costs are subject to variations depending on economic conditions. Owners and engineers tend to emphasize first-cost differences and place less significance on operating cost differences.

There are several economic analysis techniques available for a chiller purchase, but the recommended evaluation procedure, accounting for the time-value of money, is to determine estimated lifecycle costs on a “present-worth” basis. The net present value (NPV) method is superior, as it discounts all cash flows at the owner's required rate of return when evaluating mutually exclusive purchases given chiller size and project time disparities, or unequal service lives.

An important aspect of a chiller selection is analyzing its energy use for operating cash flows. Assuming a selection of a water-cooled, centrifugal chiller is required, a method to use is the chiller's relevant pressure drop and flow rate information, and its Air-Conditioning and Refrigeration Institute (ARI) integrated part load value/non-standard part load value (IPLV/NPLV) ratings. The ARI 550/590-2003: Standard for Performance Rating of Water Chilling Packages Using the Vapor Compression Cycle IPLV/NPVL ratings provide realistic off-design performance for chillers, and assists in making energy comparisons.

To illustrate, assume two 2,000-ton chillers with 25-year life expectancies operate 8,760 h/yr at $0.10/kWh; discount rate 11%; and all other items (e.g. energy cost escalation, depreciation method, maintenance costs, etc.) are equal. The manufacturers' information follows:

Use the following formulas to calculate the items necessary for a NPV comparison:

NPLV kW/ton = 1/[(0.01/A) + (0.42/B)

+ (0.45/C) + (0.12/D)]

Compressor costs

2,000 tons x (8,760 h/yr) x ($0.10/kWh)

x (NPLV kW/ton) = $/yr

Evaporator and Condenser Pumping costs

[(number ft) x (flow gpm) / (3,960 x 0.85)] x

[(0.746 kW/hp) x (8,760 h/yr) x ($0.10/kWh)] = $/yr

A NPV calculation over 25 years indicates that if Chiller 1 is selected, it would have a lifetime cost of $7.23 million, compared to Chiller 2, which would have a lifetime cost of $7.47 million. At present value (PV), Chiller 1 costs $50,541 more up front. In reviewing the cumulative lifecycle PV energy savings of operating Chiller 1, the savings of $62,804 in year 3 indicates the payback for the increase in capital expenditures occurs rather quickly. If the chillers had up-front equal costs, the energy savings would be immediate, but would not be equal to the mathematical difference of the savings if calculated using the formulas above.

The owner would need to take the difference and invest it to achieve a cash flow. The cumulative PV energy savings of operating Chiller 1 compared to Chiller 2 over 25 years is $143,300. The $240,334 is the PV difference between the two selections, taking into account all costs (not assumed equal) for this example, which is only the first cost and the energy costs carried through a 25 year NPV calculation.

A change in full or part load efficiencies can dramatically change the NPLV and operating costs. If there is a change in the NPLV for Chiller 1 to 0.507, the payback does not occur until year 17. The prediction of energy costs over a 25-year period can be a variable as anything else. The costs would be included in the NPV and discounted along with all the others equally contributed to both chillers.

Description Chiller 1 Chiller 2
Price$522,700$462,700
Evaporator pressure drop17.3 ft19.7 ft
Evaporator flow4,000 gpm4,000 gpm
Condenser pressure drop13.0 ft18.9 ft
Condenser flow6,000 gpm6,000 gpm
LoadingkW/tonkW/ton
A = 100% (85 F)0.5880.599
B = 75% (75 F)0.5050.516
C = 50% (65 F)0.4600.483
D = 25% (65 F)0.5880.595


Author Information
Schrecengost is a project manager in Stanley Consultants' Austin, Texas, office. A certified energy manager, he has extensive knowledge of lifecycle costs.




Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Boiler basics; 2017 Product of the Year winners; Manufacturing facilities Q&A; Building integration; Piping and pumping systems
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me