Power Factor No Longer a Factor for Pipe Manufacturer

An East Texas pipe manufacturer recently experienced some unexpected consequences from its modernization efforts. Managers at the company's fabrication plant, which flattens steel ingots to pipe-wall thickness, had replaced its old single-speed motor-generator sets with variable-speed drive models. The move meant greater control over the massive rolling mills, but it also resulted in current su...

12/01/2003


An East Texas pipe manufacturer recently experienced some unexpected consequences from its modernization efforts. Managers at the company's fabrication plant, which flattens steel ingots to pipe-wall thickness, had replaced its old single-speed motor-generator sets with variable-speed drive models. The move meant greater control over the massive rolling mills, but it also resulted in current surges when ingots entered one of the large machines. The surges, in turn, caused voltage sags of up to 8% on the 13.8-kV bus of the plant's motor room.

In addition to forcing nuisance tripping of other motors connected to the affected bus, these conditions also resulted in poor power-factor conditions for the entire facility. With a peak reactive power demand of almost 11 MVAR, VAR compensation was required.

Several options were considered, including fixed capacitors, an inverter-based compensator and a capacitor-based compensator. Fixed capacitors were seen as a less costly but also less complete solution, because of ongoing losses associated with capacitors always being in the circuit. In addition, these units weren't seen as capable of handling large reactive-power swings associated with the range of mill motors operating. Managers realized inverter-based compensators could handle these swings, but thought them too expensive for their needs.

A 5,000-kVAR capacitor-based compensator was the chosen option. The unit offered a 2-1/2-year payback, compared to the assumed 6-1/2-year payback of the inverter-based solution. In addition, the selected unit was more compact, allowing for closer installation to the affected mill.

The compensator was installed in January 2000 and has maintained voltage variation within +/-3.2% of nominal. Power factor is now typically above 92%, and total voltage and current harmonic distortion are now less than 10% and 5%, respectively.





No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Emergency lighting; NFPA 3 and 4; Integrated building systems; Smart lighting, HVAC design
Designing for energy efficiency; Understanding and applying NFPA 101 for mission critical facilities; Integrating commissioning and testing for fire alarm systems; Optimizing unitary pumping solutions
Economics of HVAC systems; NFPA 110-2016; Designing and choosing modular data centers
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
Driving motor efficiency; Preventing Arc Flash in mission critical facilities; Integrating alternative power and existing electrical systems
Putting COPS into context; Designing medium-voltage electrical systems; Planning and designing resilient, efficient data centers; The nine steps of designing generator fuel systems
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
click me