Playing it Safe: Fire Protection Recreation Facility

The life-safety and fire-protection systems at Bucknell University's Kenneth G. Langone Athletics and Recreation Center in Lewisburg, Pa., presented a number of challenges for the A/E design team led by EwingCole (formerly Ewing Cole Cherry Brott), Philadelphia. The result shows how a project can push the limits of conventional building codes and focus on performance objectives.

10/01/2003


The life-safety and fire-protection systems at Bucknell University's Kenneth G. Langone Athletics and Recreation Center in Lewisburg, Pa., presented a number of challenges for the A/E design team led by EwingCole (formerly Ewing Cole Cherry Brott), Philadelphia. The result shows how a project can push the limits of conventional building codes and focus on performance objectives.

Chief among the challenges for code compliance were:

  • Separations between existing building sections and the new fitness center, natatorium and a 4,000-seat pavilion—a combined floor area of about 130,000 sq. ft.

  • A phased construction and occupancy plan that required operational fire protection systems in sections of the building remote from new incoming services as well as maintenance of exits.

  • The development of a fire-protection and life-safety program that met the intent—if not the letter—of two different building codes enforced by two separate authorities having jurisdiction (AHJs).

The building site in East Buffalo Township falls under the jurisdiction of both the Union County Code Administration (UCCA) and the Commonwealth of Pennsylvania Dept. of Labor & Industry (L&I). The UCCA enforced the 1999 Edition of the BOCA National Building Code and L&I enforced the Fire and Panic Regulations, a document loosely modeled on early editions of the NFPA Life Safety Code.

During the schematic design phase, it became apparent that strict compliance with the Fire and Panic Regulations would be problematic. To resolve the conflicts, meetings were held with the UCCA code administrator and L&I to discuss the compliance strategy and to establish the 1999 BOCA Building Code as the guiding document. Variances were obtained from L&I for occupant load calculations, exit width requirements, maximum travel distances, exit access corridor ratings, use of communicating stairs as exits and vertical openings.

Although the BOCA code more closely addressed the unique features of the building, certain elements presented a challenge for strict compliance and forced a focus on fire safety performance. Key among these issues was that a new three-story atrium space would connect the existing and new building sections. Portions of the existing gymnasium contained unprotected structural steel that would have been impractical and cost-prohibitive to protect, but the new building area would significantly exceed the maximum allowable area per BOCA for 2C construction. This problem was further complicated by the goal of keeping the existing brick exterior wall and windows of the gymnasium offices intact.

The building's code-relevant fire safety systems were based on the requirements of the BOCA code. Additional features were also installed to support an increased focus on performance. All of the new construction and major portions of the existing building sections were sprinklered, including the area over the new pavilion's event floor. While the code would have permitted omission of sprinklers over this area, a review of the potential fire loads during special events led to the inclusion of sprinklers for protection of structural steel and fire control.

(For the full story, visit the web at www.csemag.com .)





No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
integrated building networks, NFPA 99, recover waste heat, chilled water systems, Internet of Things, BAS controls
40 Under 40; Performance-based design; Clean agent fire suppression; NFPA 92; Future of commissioning; Successful project management principles
BIM coordination; MEP projects; NFPA 13; Data center Q&A; Networked lighting controls; 2017 Product of the Year finalists
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me