Not Again – E-Stops Do Not Equal Machine Safety

How many times does this issue come up? An e-stop device is not a safety device! Therefore, it’s not a part of the safety related parts of a control system (SRP/CS). Then, why is an e-stop device so often confused as being part of the safety design for a machine?

07/20/2011


Jokab Safety giant E-Stop at Pack Expo 2010How many times does this issue come up? An e-stop device is not a safety device! Therefore, it’s not a part of the safety related parts of a control system (SRP/CS). Then, why is an e-stop device so often confused as being part of the safety design for a machine?

JB Titus, CFSE     In my opinion, we should first look at the term, Functional Safety. “Functional Safety” was introduced to industry by IEC 61508: 1998. IEC 61508, Functional Safety of Electrical/Electronic/Programmable Electronic Safety-related Systems, defines it as the following. IEC 61508 Definition:

  • Safety is the freedom from unacceptable risk of physical injury or of damage to the health of people, either directly, or indirectly as a result of damage to property or the

environment.

  • Functional Safety is part of the overall safety that depends on a system or equipment operating correctly in response to its inputs.

Elobau E-stop switches     In a functional safety system there are electrical and electronic components like; safety relays, interlock switches, safety contactors, safety PLC’s and drives, safety motion scanners and light curtains, and safety net works. All of these technologies are then designed to form a safety system and are dedicated to perform specific safety functions. These safety functions are usually determined as required to mitigate certain hazards identified by the risk assessment process.

Carlo Gavazzi e-stops     Not mentioned above is the e-stop device. I believe that’s because e-stops have a broader range of application, must be manually activated, and are not dedicated to perform a safety function. The colors, red push buttons with a yellow background, may be confusing. But, they are not required and applied to always perform safety-related functions. According to NFPA 79; 2007, Electrical Standard for Industrial Machinery, e-stops are required for “final removal of power to the machine actuators” to achieve either a Category 0 or Category 1 stop (Clause 9.2.2 Stop Functions and Clause 9.2.5.4.1 Emergency Stop). Many times the e-stop may be activated due to non safety-related functions, such as; material feed issues, impending machine jams, maintenance issues, or machine set-up requirements.

     Does this help clarify the often misunderstood e-stop versus safety device issue?

     Your comments or suggestion are always welcome so please let us know your thoughts. Submit your ideas, experiences, and challenges on this subject in the comments section below. Click on the following text if you don't see a comments box, then scroll down: Not Again – E-Stops  Machine Safety.

     Did you see the Safety Integration Webcast?

     Related articles:

E-Stops and Your Compliance

E-Stops Aren’t Safety Devices

How to Integrate Safety

     Contact: www.jbtitus.com for “Solutions for Machine Safety”.



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Boiler basics; 2017 Product of the Year winners; Manufacturing facilities Q&A; Building integration; Piping and pumping systems
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me