NEC Chapter 2: Wiring and protection

08/14/2013


Identifying grounded conductors 

For insulated grounded conductors of 6 AWG or less, the conductor must be manufactured to meet the identification requirements. Namely, it must have a continuous white or gray outer finish or three white stripes along the entire length of the conductor. There are other options for mineral-insulated (MI) cable, photovoltaic (PV) power systems, fixture wires, and aerial cable.

  1. MI due to nature of construction requires re-identification at terminals
  2. Single-conductor, sunlight-resistant outdoor cable for PV systems allows distinctive white markings at terminations (690.31)
  3. Fixture wire allows ridges for the grounded conductor among other color options detailed in 400.22
  4. Aerial cable may be identified by a ridge on cable. 

Conductors larger than 6 AWG also require white or gray outer finish or three white stripes along the entire length of the conductor, but there is an option to re-identify the conductor by wrapping the cable with white or gray at termination points. Paint, tape, or shrink tube are good options. Just be sure the identification completely circles the conductor.

Where grounded conductors of two different systems are in the same raceway or enclosure, they must be identified differently from each other (200.6 D). Identification requirements are the same as explained above, plus there is an option to have a colored stripe other than green running along the insulation. Color code labels are required at junction boxes and at termination equipment. An example color code table:

Alternate uses for conductors

Conductors for systems greater than 50 V, identified by the manufacturer with white or gray, may be used for alternate purposes under the following conditions:

  • Conductors within a cable assembly that are not switched. Supply to the switch is allowed but return from switch is not.
  • Flexible cords as permitted in 400.22. 

Figure 4: This is a switched receptacle for a chain-hung fixture. The white conductor in NM cable has been re-identified with red tape and is connected to a hot conductor. Courtesy: CH2M HillWhere the grounded conductor is repurposed, it must be identified by encircling the conductor with a color other than white, gray, or green. Red tape is commonly used and paint is listed as an option; red shrink tube is a cleaner installation and it doesn’t fall off. The white conductor can only be used as the ”energized” leg to the switch. Troubleshooting the circuit and finding potential to ground on the white conductor clues the technician that this is a switch leg. Another advantage is that you end up with standard color coding at the device. This helps avoid confusion as to the purpose of the white conductor at the switch because it is energized under operating conditions. This practice is going to be less common because the 2011 NEC now requires that the grounded conductor also be carried to the switch and standard nonmetallic cable assemblies have only one neutral. 404.2 C is outside the scope of this article (see Figure 4). 

This receptacle is switched and common nonmetallic cable was used for a switch leg. Red tape was used to re-identify the ungrounded conductor. At the switch, while the circuit is energized, voltage can be found on the white repurposed wire.



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Boiler basics; 2017 Product of the Year winners; Manufacturing facilities Q&A; Building integration; Piping and pumping systems
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me