Multi-Purpose Comfort for Multi-Use Stadium

As the home of four professional sports teams, the Staples Center in Los Angeles can experience up to 10 days each season where multiple events occur on a single day. Therefore, its 35-person crew needs to be able to change the venue from hockey to basketball in less than two hours, including installation or removal of extra seating.

01/01/2002


As the home of four professional sports teams, the Staples Center in Los Angeles can experience up to 10 days each season where multiple events occur on a single day. Therefore, its 35-person crew needs to be able to change the venue from hockey to basketball in less than two hours, including installation or removal of extra seating.

The facility's seating, concessions, lighting and sound systems were all designed to maximize a visitor's experience. Not so obvious to the spectators, but just as important for their comfort, is the HVAC system.

'Chill out' in L.A.

M.E. Engineers/Hayakawa Associates of Los Angeles designed a system that includes low chilled-water and supply-air temperatures and features three high-efficiency 833-ton chillers using HCFC-123. Cooling towers for the units are based on an 82.5°F to 94.6°F range and operate on a 2.3 gpm/ton flow rate. This design improves overall system efficiency by reducing pump and fan power requirements over more traditional 3.0 gpm flow rates.

The centrifugal chillers deliver chilled water in the range of 40°F to 42°F to the air handlers for most arena events, and at 36°F for hockey games and ice rink shows. Lower chilled-water temperatures during rink events assures dehumidification to help maintain the surface quality of rink ice. With this low temperature water, supply air is delivered to the space at 40°F for ice rink events and at 45°F for others.

In addition to the centrifugal units, a 300-ton screw chiller is used when chilled-water demand is low, typically at times when the arena is not in use.

Air handlers, with 12-row chilled-water coils, are the main source of dehumidification of building air. Other types of air handlers supply restaurants, retail areas, locker rooms and office areas.

In addition to general seating areas, there are 160 luxury suites, each with variable-air-volume boxes and electric reheat and ventilation air provided by a dedicated duct system.

Acoustical comfort

Guaranteeing the right climate is the major challenge for the HVAC system, but acoustical comfort is also a significant issue for HVAC designers. "We book a wide range of events, not just sports contests," explains Bill Pottorff, the facility's chief engineer. "It's important that ambient sound be held as low as possible."

In this respect, Pottorff says, the acoustical and comfort levels produced by the facility's plant has exceeded all expectations.





No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Emergency lighting; NFPA 3 and 4; Integrated building systems; Smart lighting, HVAC design
Designing for energy efficiency; Understanding and applying NFPA 101 for mission critical facilities; Integrating commissioning and testing for fire alarm systems; Optimizing unitary pumping solutions
Economics of HVAC systems; NFPA 110-2016; Designing and choosing modular data centers
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
Driving motor efficiency; Preventing Arc Flash in mission critical facilities; Integrating alternative power and existing electrical systems
Putting COPS into context; Designing medium-voltage electrical systems; Planning and designing resilient, efficient data centers; The nine steps of designing generator fuel systems
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
click me