Manufacturers' focus: Sports, entertainment venues

04/24/2013


CSE: Integration of facilities is becoming more prevalent. How is your company/product meeting this need?

Cummins Power Generation: At Target Field, the generators and transfer switches are networked with the building management system, so critical information about the status of the power sources can be monitored from the facility command center.

Uponor: As previously noted, we recognize the importance of proper controls to ensure that the systems operate as intended. We work hand in hand with the control system providers on each project to ensure that the proper sequence of operation is incorporated.

CSE: Describe some recent electrical/power system challenges you encountered when designing a new building or updating an existing building.

Cummins Power Generation: Target Field was shoe-horned into an extremely tight site on the edge of downtown Minneapolis. Locating the emergency generators was a challenge. There are two generators at opposite ends of the building, each backing up half of the facility’s load. Both are located under city streets, and one generator is located in an enclosed space that required a long run of special piping to bring in fresh air from the pedestrian concourse above, and to vent the exhaust out over a nearby freeway.

CSE: Large entertainment venues traditionally require a great deal of power during events. What resources can you offer engineers to help meet these short-duration, high-power goals?

Uponor: Yes, I think there are some folks in New Orleans who know a little something about that. One of the great benefits of hydronic-based systems is that they use a fraction of the energy required versus air-based heating systems. This can help alleviate the total load placed on the facility’s power system.

Cummins Power Generation: Given the varying power levels required at multi-purpose stadiums, it makes sense to plan on renting generators for major events. This year’s Super Bowl is a great example. CBS’s on-site equipment and Beyonce’s halftime show were both powered by rental generators; they were not connected to the stadium’s utility feed and therefore had no connection to the stadium power failure.

CSE: How have the costs and complexity of fire protection systems changed in recent years?

Notifier: Over the past decade, more fire alarm and life safety systems are using networked panels. This adds the flexibility to add new panels quickly as a facility expands. Networking also adds survivability to the life safety system because the system is spread throughout a building rather than being concentrated in a single area. If there was an event where the entire system is located, safety could be compromised. With a distributed system, the equipment outside the event area will continue to function normally. Survivability is an important feature that many building owners or facility managers are looking for today in a fire or life safety system. Another advantage of networking is ease of adding a PC-based workstation to the entire system. With a workstation the end-user has a graphical representation of the entire protected facility and can monitor the event as it unfolds, then make decisions on a response in real time. Adding networking and workstations can raise system design and equipment cost, but most buildings are willing to accept the extra expense for the benefit of improved life safety.

CSE: With regard to mass notification and emergency communication systems, what code changes do you anticipate in the near future?

Notifier: The 2010 Edition of NFPA 72, the National Fire Alarm and Signaling Code, added a new chapter, Chapter 24, dedicated to emergency communication systems. The demand for more definition of the need for and requirements of mass notification or emergency communications systems has been increasing since the mid 1990s as a result of terrorist and mass casualty incidents around the world. As more jurisdictions adopt NFPA 72-2010 and the latest version, NFPA 72-2013, more facilities will be required to have emergency communication systems that deliver emergency messages through multiple means such as voice announcements, e-mail blasts, text messages, etc., to ensure that every person is reached with the announcement whether they work in a facility, are visiting, or are in the nearby area. Having a single method of communication will no longer be adequate.

CSE: What new detection, suppression, or notification system, product, or method do you see becoming the most prevalent? Describe a recent project.

Notifier: A detection trend that is gaining traction is the use of multi-criteria detection. An example of a multi-criteria detector is a combination smoke detector with photo, infrared, temperature, and carbon monoxide sensors in a single device. Algorithms in the device use the outputs of each sensor to verify that the multiple signatures of a fire are present before sending an active fire signal to the fire alarm control panel. Multi-criteria detection can further reduce nuisance alarms, and if programmed to do so, can report out the levels of each different type of sensor. In this example the CO sensor could report actual CO levels to the panel, eliminating the need for a separate CO detector. This reduces installation and maintenance costs along with improving aesthetics for the building owner or project architect.

CSE How does your technology help engineers make their clients’ sports and entertainment structures more energy efficient?

Uponor: A radiant heating and cooling system can help dramatically reduce the energy consumption of a building through lower transport energy usage, more efficient operating modes, expanded room setpoints, lower transmission losses, and thermal inertia. Because the heat-transfer capacity of water is much higher than that of air, a radiant system that uses a pump to move water (in lieu of a fan to move air) can achieve the same heat transfer using significantly less energy.

CSE: What HVAC issue comes to the forefront most when you’re supporting engineers in such facilities? How do you help overcome these issues/answer their questions?

Uponor: When an engineer is considering radiant cooling, one of the common issues that seems to come up is surface condensation. Condensation on the floor is both a safety and a maintenance concern. This would occur if the surface temperature ever dropped below the dewpoint. This is of particular concern in high-occupancy areas such as sporting or entertainment venues, where the latent load could be significant. In order to address this, however, one needs to look at the HVAC system as a whole. If the system is properly designed to maintain temperature and relative humidity levels conducive to human health and comfort, then it would be unlikely that you would have indoor dew points close to the 66 to 68 F minimum floor surface temperature recommended by ASHRAE Standard 55


<< First < Previous 1 2 Next > Last >>

No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
2014 Product of the Year finalists: Vote now; Boiler systems; Indirect cooling; Integrating lighting, HVAC
High-performance buildings; Building envelope and integration; Electrical, HVAC system integration; Smoke control systems; Using BAS for M&V
Pressure piping systems: Designing with ASME; Lab ventilation; Lighting controls; Reduce energy use with VFDs
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Consulting-Specifying Engineer case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Protecting standby generators for mission critical facilities; Selecting energy-efficient transformers; Integrating power monitoring systems; Mitigating harmonics in electrical systems
Commissioning electrical systems in mission critical facilities; Anticipating the Smart Grid; Mitigating arc flash hazards in medium-voltage switchgear; Comparing generator sizing software
Integrating BAS, electrical systems; Electrical system flexibility; Hospital electrical distribution; Electrical system grounding
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.