Machine Safety: Can one channel mitigate a Cat 3/PLd functional requirement?

Category 3 and 4 architectures typically call for a control reliable (that is, redundant) circuit design no matter what safe logic solver under consideration: safety relay, safety PLC, safe drive, and so forth. So why would there be any confusion?

07/02/2014


Figure 5 in ISO 13849-1; 2006 clearly shows how these factors can impact a safety circuit’s design.Category 3 and 4 architectures typically call for a control reliable (that is, redundant) circuit design no matter what safe logic solver you’re considering, such as a safety relay, safety PLC, safe drive, and so forth. So, why is there confusion?

 

I have seen people be confused at the differences between an application design and the individual design of a sub-system by a supplier, such as a safety PLC. Over the past 10 years or the term “control reliable” has drifted away. Redundancy or duality seems to have taken its place along with monitoring and diagnostics coverage. Haven’t we all seen where redundancy or duality has meant two safe inputs and two safe outputs connected by a safety certified logic solver for a Cat 3 or 4 architecture? And of course the safety certified logic solver had to meet the design requirements of IEC 61508, and it had to be listed for use in machine safety applications. In the past few years since ISO 13849-1 & 2; 2006, the extent of monitoring and diagnostics coverage needs to be considered within the safety circuit as well as within a sub-system.

Confusion introduced

Other factors also can be considered by a designer but isn’t this enough to introduce confusion? WHY? Because, not all designs by suppliers of sub-systems like safety PLCs are alike. This is where the safety data parameters from the supplier can play a role. One supplier of a sub-system can perform some of the monitoring and diagnostics coverage within their safety logic solver to have a single safe (enough) output in certain circumstances. Additionally, couldn’t that single safe output in certain circumstances be fed dually to two contactors? If the answer is yes, and the overall safety circuit can be verified as meeting the performance level requirements of PLd, haven’t we mitigated a Cat 3/PLd functional requirement with a single channel output?

As the graphic shows, The overall effect of analyzing a complete safety circuit’s performance including its MTTFd (mean time to fail dangerous) and its DCavg (diagnostics coverage average) along with the safety data parameters of all components and sub-systems can impact the answer to this question. Figure 5 in ISO 13849-1; 2006 clearly shows how these factors can impact a safety circuit’s design. Having said that, don’t we often simply error to the high side and provide redundancy or duality throughout a Cat 3/PLd safety circuit? I have found that the best recommendation is to always consult with the supplier of a safety certified sub-system regarding the design integrity of their safe outputs.

What are your thoughts about safety circuit design? Do you have related questions or suggestions? Add your comments or thoughts to the discussion by submitting your ideas, experiences, and challenges in the comments section below.

Related articles:

LinkedIn – Safety Automation Forum, When is dual channel allowed to be single channel?

Machine Safety: When should 2 mechanical safety switches be used on an access door?

Control Engineering, Safety control systems: Essential considerations, costs

Contact: www.jbtitus.com for “Solutions for Machine Safety.”



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
MEP Giants; MEP Annual Report; Mergers and acquisitions; Passive, active fire protection; LED retrofits; HVAC energy efficiency
Integrating electrical and HVAC systems; Tracking and conserving facility water use; Energy code advancements; The future of professional engineers
Control noise, vibration in building design: Tackling acoustics and design issues; High-performance building design; NFPA 99; Combined heat, power
Putting COPS into context; Designing medium-voltage electrical systems; Planning and designing resilient, efficient data centers; The nine steps of designing generator fuel systems
Designing generator systems; Using online commissioning tools; Selective coordination best practices
Understanding transfer switch operation; Coordinating protective devices; Analyzing NEC 2014 changes; Cooling data centers
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
click me