Liquid transformers--the right stuff

In this installment, Guentert gives more reasons for the differences in reliability between liquid transformers and dry-types.

05/23/2012


 

Elbow-Type MOV’s Connected Directly to Primary Windings

We left off last week discussing some of the possible reasons for differences in reliability of liquid transformers versus dry-types, when primary windings are switched by vacuum circuit breakers (all my personal opinions, again). Here are more reasons:

 

1. On all data center projects I’m involved with, we very carefully watch the installation details of the “system,” not just the transformer itself. Using the “loadcenter” concepts discussed earlier, moving the transformations into very close proximity to the loads has the effect of not only reducing high costs of the large secondary feeders, but generally has the added benefit of LENGTHENING the primary feeders, creating “Nature’s Own Snubber” by adding shunt capacitance to the shielded MV cables.

 

2. Then, we always connect a very good set of MOV surge arrestors DIRECTLY to the primary winding terminals. The capacitance of the cables flattens out the extremes of (dv/dt) rate-of-rise, to allow the arrestors to do their job in clamping the surge voltage as the transient develops across the windings. (Many consulting engineers still place arresters on the load runback connections of upstream vacuum breakers – at the source ends of the cables - where they are ineffective. Maximum effectiveness is when the arresters are connected directly to the transformer primary windings.  Remember, this is not a transient voltage entering the windings from upstream at the vacuum breaker.  Instead, the transient is developed within and across the winding itself, and this event occurs with such extreme speed that the winding insulation is damaged before the voltage wave can travel all the way back upstream through the cables to the arresters at the breaker.)

 

3. And, also importantly, we use only vacuum breakers from manufacturers who have performed their due diligence through R&D to ensure that the metallurgy of the power contacts inside their vacuum bottles has the “right stuff” to minimize current chopping and re-ignition phenomena during switching operations.

 

Typical Fan-Cooled, Ventilated Dry-Type Transformer4. Almost all modern VPI dry-type transformers are ventilated and air-cooled, usually by simple convection, sometimes with supplemental forced air from cooling fans. Either way, air is drawn into the lower vents, then either convects or is blown by fans directly over the transformer windings. The problem is, as that happens, microscopic particles of airborne contaminants are deposited on the primary windings, reducing the overall dielectric strength of the insulation system over time, and encouraging partial discharges during large transient events. If a ventilated transformer begins its life with a primary BIL of 110  kV, the BIL can degrade significantly within a few years, unless there is very frequent cleaning and maintenance. (It’s my experience that the majority of the failures I investigated occurred between one and three years after the failed unit had been initially placed into service. When I asked the question, I learned that practically none of them had been ever been maintained and cleaned.)

 

Liquid transformers, on the other hand, have their windings immersed in clean fluid within a sealed tank, so external airborne contaminants and moisture can’t get to the windings. (Use of an epoxy cast resin transformer also eliminates much of this problem.)



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
High-performance buildings; Building envelope and integration; Electrical, HVAC system integration; Smoke control systems; Using BAS for M&V
Pressure piping systems: Designing with ASME; Lab ventilation; Lighting controls; Reduce energy use with VFDs
Smoke control: Designing for proper ventilation; Smart Grid Standard 201P; Commissioning HVAC systems; Boilers and boiler systems
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Consulting-Specifying Engineer case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Protecting standby generators for mission critical facilities; Selecting energy-efficient transformers; Integrating power monitoring systems; Mitigating harmonics in electrical systems
Commissioning electrical systems in mission critical facilities; Anticipating the Smart Grid; Mitigating arc flash hazards in medium-voltage switchgear; Comparing generator sizing software
Integrating BAS, electrical systems; Electrical system flexibility; Hospital electrical distribution; Electrical system grounding
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.