Letters: Reader Feedback

Important NEC exclusion In your Codes and Standards story "New NEC Could Change Emergency Power Distribution System Design" (CSE 8/05, p.21), you neglected to mention a section 700 paragraph that is certain to have a significant impact on the design of emergency feeders. 700.9(D)(1), for buildings that exceed 75 ft.

11/01/2005


Important NEC exclusion

In your Codes and Standards story "New NEC Could Change Emergency Power Distribution System Design" ( CSE 8/05, p.21 ), you neglected to mention a section 700 paragraph that is certain to have a significant impact on the design of emergency feeders.

700.9(D)(1), for buildings that exceed 75 ft. in height and places of assembly of 1,000 persons or more, requires that emergency feeders be in spaces or areas that are protected by an approved automatic fire suppression system. Comments in the handbook distinguish this change from 2002: Previously, it required wiring to be in buildings that were fully protected by an approved automatic fire suppression system. However, such buildings may have spaces, such as a space above a suspended ceiling, that are not fully protected by the suppression system. The revised wording clarifies that the wiring must be in a space that is protected by the automatic suppression system .

BARRY O'CONNELL P.ENG., TYCO THERMAL CONTROLS





No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
integrated building networks, NFPA 99, recover waste heat, chilled water systems, Internet of Things, BAS controls
40 Under 40; Performance-based design; Clean agent fire suppression; NFPA 92; Future of commissioning; Successful project management principles
BIM coordination; MEP projects; NFPA 13; Data center Q&A; Networked lighting controls; 2017 Product of the Year finalists
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me