Curbing contaminant carryover I was interested in and enjoyed your article "A New Lab Formula" (CSE 3/06, p. 24). I am curious about the heat wheel technology you refer to. How do you get around the cross-contamination between airstreams? GREG HOLMES, P.E., R.P.A. OPERATIONS MANAGER, JONES LANG LASALLE CORPORATE, PROPERTY SERVICES Michael J.

06/01/2006


Curbing contaminant carryover

I was interested in and enjoyed your article "A New Lab Formula" ( CSE 3/06, p. 24 ). I am curious about the heat wheel technology you refer to. How do you get around the cross-contamination between airstreams?

GREG HOLMES, P.E., R.P.A. OPERATIONS MANAGER, JONES LANG LASALLE CORPORATE, PROPERTY SERVICES

Michael J. Dausch, P.E., MBA, director of design and construction for Johns Hopkins School of Medicine in Baltimore, which employs multiple energy-recovery wheels, responds:

Johns Hopkins began by using a total energy-recovery wheel designed specifically for lab type environments by SEMCO, Inc. The wheel utilizes a 3-angstrom molecular sieve technology that has the capability of avoiding the transfer of airborne contaminants contained in the lab exhaust air. Other technologies do not have this capability.

We first initiated a pilot test site of this technology more than 15 years ago on a small laboratory requiring approximately 15,000 cfm of outdoor air. Our health and safety department tested this system extensively to ensure that contaminant carryover did not occur. The following year we constructed our first major laboratory facility using this technology to precondition approximately 400,000 cfm of outdoor air.

These systems, located in our Ross Research Facility, were recently tested for both recovery performance and contaminant carryover as part of a Labs21 presentation, which can be viewed at www.labs21century.gov/conf/past/2003/presentations/a3_fischer.pdf .

Despite years of operation, the findings confirmed that the recovery performance had not diminished. The independent air quality testing confirmed that recovery wheels did not transfer contaminants from the exhaust airstream into the supply airstream.

Since that time, we have utilized the 3-angstrom molecular sieve total-energy wheel for many major laboratory projects—over one million total sq. ft.—with great success. In addition, SEMCO has completed a significant amount of research to address the concern for desiccant wheel carryover, which you can view at semcoinc.com .

Not on the schedule

The sidebar "Improved Smoke Ventilation at Atlanta's Airport" ( CSE 4/06, p. 56 ) indicates a bad operating schedule! It is well-known that rotating machinery has maximum stress during starting.

These ventilating fans will last a whole lot longer if they are alternately run for a one- or six-month period instead of only a week!

RCA determined this for 1,000-hp air compressors in the early 1970s in Marion, Ind.

CHUCK MUHLEMAN, PRESIDENT (RETIRED), PRESS CONTROLS CORP., HUNTSVILLE, ALA.





No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
BIM coordination; MEP projects; NFPA 13; Data center Q&A; Networked lighting controls; 2017 Product of the Year finalists
Emergency lighting; NFPA 3 and 4; Integrated building systems; Smart lighting, HVAC design
Designing for energy efficiency; Understanding and applying NFPA 101 for mission critical facilities; Integrating commissioning and testing for fire alarm systems; Optimizing unitary pumping solutions
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
Driving motor efficiency; Preventing Arc Flash in mission critical facilities; Integrating alternative power and existing electrical systems
Putting COPS into context; Designing medium-voltage electrical systems; Planning and designing resilient, efficient data centers; The nine steps of designing generator fuel systems
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
click me