Insulation for Pipe and Duct Applications

Insulation is available in numerous materials suitable for various applications. Many variables play a part in selecting the insulation for a specific application. When selecting insulation, review the following questions:

10/01/2004


Insulation is available in numerous materials suitable for various applications. Many variables play a part in selecting the insulation for a specific application. When selecting insulation, review the following questions:

  1. What is the temperature difference between the fluid being conveyed and its environment? This can range from 20°F to more than 2,000°F.

  2. Where is the insulation located? Is it indoors or outdoors?

  3. What is the insulation's environment like? Does it need a protective jacket to guard it from humidity, building occupants, etc.? Is it located in a high traffic area?

  4. What are the cost implications for using the insulation? Is it readily available? Is it easy to install? Are large quantities of insulation required?

Insulation Types

Fiberglass

Mineral Wool

Elastomeric Cellular Foam

Polyisocyanurate

Hydrous Calcium Silicate

Application

Primarily used indoors with a vapor barrier. Can be used for piping or ductwork. Durability is low. Loses insulation effectiveness when wet. Installers are required to take protective measures for installation.

Primarily used in high temperature applications such as generator exhaust stacks and incinerator breechings. Commonly used in Europe in lieu of fiberglass. Also used in equipment such as sound attenuators.

Primarily used for cold applications such as refrigerant piping, chilled-water piping, chiller evaporator bundles, storage tanks and exterior ductwork. Maintains insulation effectiveness when wet. No protective requirements for installers.

Primarily used in cold applications. Good vapor resistance and will maintain insulation characteristics when wet. Durable product for easy maintenance when provided with PVC jacketing.

Primarily used in high temperature applications such as generator exhaust stacks, incinerator breechings, boiler flues and grease exhaust ducts.

Outdoor Use

Not recommended without weathertight covering

Not recommended

Not recommended without UV protective covering

Not recommended without weathertight covering

Not recommended without weathertight covering

Recommended Temperature Restrictions

0°F to 450°F

Ambient (70 °F) to 1,200°F

0°F to 140°F

-250°F to 200°F

Ambient (70 °F) to 1,200°F

Vapor Resistance

No vapor resistance without vapor covering

No vapor resistance without vapor covering

Good vapor resistance

Good vapor resistance

No vapor resistance

K-Value/Inch

0.24 K-value at 75°F

0.30 K-value at 200°F

0.28 K-value at 75°F

0.19 K-value at 75°F

0.40 K-value at 300°F

Approximate Cost

Lowest Cost

60% to 80% higher than fiberglass. Ceramic fiber for high temperatures

30% to 60% higher than fiberglass based on pipe size and insulation thickness

5% to 40% higher than fiberglass based on fitting cost and size

60% to 80% higher than fiberglass. For high temperatures





No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
BIM coordination; MEP projects; NFPA 13; Data center Q&A; Networked lighting controls; 2017 Product of the Year finalists
Emergency lighting; NFPA 3 and 4; Integrated building systems; Smart lighting, HVAC design
Designing for energy efficiency; Understanding and applying NFPA 101 for mission critical facilities; Integrating commissioning and testing for fire alarm systems; Optimizing unitary pumping solutions
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
Driving motor efficiency; Preventing Arc Flash in mission critical facilities; Integrating alternative power and existing electrical systems
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me