Getting analytical on labs

This article summarizes trends and considerations to be mindful in relation to the physical environment in which analytical labs operate.

09/12/2016


The past few years have yielded some interesting trends in the design and operation of analytical laboratories in the corporate biopharmaceutical marketplace. This article summarizes those trends and some considerations to be mindful of as it relates to the physical environment in which analytical labs operate.

1. Compartmentalization

Research operations are increasingly compartmentalized. Lab waste, glassware, consumables, sample and material movement, instrument maintenance and calibration, and other complementary functions are commonly handled by third parties on most major biopharmaceutical campuses. Analytical operations interfacing with these groups present logistics, efficiency, security, and bioburden challenges. In some instances, third-party costs will increase (e.g., manpower needs increase) if travel distances are too great or gowning and security logistics drastically reduce efficiency. Maintaining a clean environment requires clear segregation of travel for third parties coming from the outside, especially in biologically sensitive environments.

The graphic below is a sample adjacency diagram from a recently completed consolidation project. As you can see, when mapping out future/renovated operations, one must consider much more than the lab itself, at times looking as far out as the loading dock and even into adjacent buildings.

Figure 1 - Sample Lab Adjacency Diagram. Courtesy: CRB

The diagram also demonstrates the need to properly locate queuing points and other handoff or interaction zones between scientific personnel and various third parties. These nodes help address security and bioburden concerns while simultaneously improving efficiencies for both sides.

Although the enclosed diagram represents a unique operation, the considerations are applicable across a spectrum of analytical groups and clients. Moreover, it stresses the importance of including leadership or representatives from the various third parties in your initial programming and planning sessions.

2. Process-centric vs. project-centric

Market pressure for return on investments in research and development (R&D) has, in some instances, driven a shift from analytical operations being process-centric (e.g., where operations personnel concentrated on a step or subprocess of the overall analytical work stream) to being more project-centric. In the project-centric environment, manpower is streamlined (i.e., reduced) and cross-trained over various technologies, and those same individuals are tasked with the end-to-end completion of the analysis—not just an individual step.

This project-centric environment, where personnel stay with the sample from receipt/intake through testing completion, drastically changes the flow within the lab. Although multiple queuing areas within the lab now go away, travel paths and shared instrument utilization become critical analysis points.

The figure below is a screenshot from an analysis performed on an analytical-testing lab. The client was interested in modeling their current lab operations to determine equipment and personnel impact from a pending increase in sample volume.

Figure 2 - Testing Lab Optimization Graphic. Courtesy: CRB

The graphic, which represents a blend of CRB's lab-planning and operations-improvement expertise, allowed for a data-driven analysis of testing equipment utilization, test-prep area congestion, travel paths, and sample-handling efficiency.

The analysis demonstrated that with some simple process-flow improvements, no additional staff, instruments, or lab renovations were required to handle the increased sample volumes.

From this analysis, it was determined that:

  • The lab could handle insourcing (163% additional testing throughput) with their current labor and equipment.
  • With two additional fume hoods and an additional analyst, the new product could be accommodated (including the insourced tests, a total of 230% additional testing throughput).

Without this analysis, the client wouldn't have been able to make a data-driven decision to keep outsourcing tests or buy new lab equipment, etc. In effect, there was a cost avoidance (by not buying new lab equipment that wasn't needed) and a cost savings by insourcing tests.

3. Contract employees and standardized testing

Numerous biopharmaceuticals use in-house contract employees to execute standardized analytical-testing procedures. These tests are still critical to R&D operations, and their location still requires similar adjacencies to the balance of noncontracted testing; however, the integration of those testing functions carries a unique wrinkle. Although mostly an organizational-structure issue, some interpretation of labor laws suggest these contracted personnel should be managed and operate somewhat independently of noncontracted (i.e., full-time, direct-hire, employee-run) operations.

Figure 3 - Analytical Adjacency Diagram. Courtesy: CRBThis influences the planning considerations for analytical functions if a portion of the testing is by contract personnel. In contrast with this labor-law-inspired segregation is the inherent desire to colocate common testing, instruments, and personnel.

Whether contract or not, it is more efficient to cluster personnel based on technical objectives, especially in analytical environments where standardized tests are most commonly developed by full-time, direct-hire employees. Otherwise, you spend more capital on additional square footage for segregating these spaces and providing additional egress space.

The graphic at the right represents an analytical-testing group who, in this instance contracted with PPD. As the graphic shows, there are more layers to the planning of their new facility than what would have been expected 5 years ago. A balance is struck between colocating contract employees and clustering analytical functions. Again, much like with the third-party coordination issues, its best to include representation from the contract organization in your early planning/programming effort.

4. Density, chemical quantity

As testing becomes standardized and testing volumes increase, equipment quantities drive more dense laboratory environments. Although not as chemically heavy as some of their discovery/chemistry peers, analytical laboratories are finding themselves pushing the limits of allowable solvents. Traditionally, in a larger lab program, heavier chemical/solvent users were placed on lower-floor levels where code-driven volume limits were less stringent. Analytical functions fell outside this "heavy user" classification, therefore, they were free to be placed on higher floors.

Figure 4 - High-Density HPLC Lab. Courtesy: CRBBased on more dense configurations, like the one in the image to the left, stored chemical quantities can quickly approach the limitations of those higher floors. As shown in the picture, each instrument uses dedicated solvents and dedicated waste collection. Amplifying the issue is the consideration by many biopharmaceutical Environmental Health and Safety (EH&S) departments that a waste container is "full" even if only partially full. The density of equipment and method of chemical calculation has the potential to eclipse the quantity limit for the analytical function, especially if on a higher-level floor.

Working closely with EH&S personnel to properly quantify the actual chemical quantities present is a good first step. Increasing the frequency of waste collection and limiting solvent storage at local queuing points are other strategies to stay below the limit. Additional steps can be taken by defining the in-use versus storage quantities and making proper use of chemical storage cabinets. Another option involves adding control areas via fire-rated walls, but this adds cost to the project. Lastly, consideration should be given to integrating a solvent-collection system with a termination point remote from the control zone of the analytical environment.

5. Analytical-development feedback loop

Analytical laboratories within the biopharmaceutical market are always part of a bigger operation or business unit. Best practices developed within analytical-testing operations are being sought after by peer organizations. The desire to have multiple peer groups in close proximity to analytical functions and the accompanying knowledge sharing that results puts pressure on early planning phases to ensure proper adjacency and connectivity.

In a larger R&D planning effort, this became a challenge of scale. Several distinct development groups requested close adjacency to their analytical peers for the benefits listed above. Each development group's lab footprint (qty. 6) ranged from 6,000 to 10,000 sq ft. When blended with their office and support requirements, the net technical program exceeded 150,000 sq ft. Clearly, to achieve the adjacency desired across the board, horizontal and vertical connectivity would need to be considered.

Figure 5 - Conceptual building Section. Courtesy: CRBThe graphic at the right is a conceptual representation of one of the proposed solutions taking into account a couple of program-specific factors. First, the ratio of lab to office was approximately 2:1. Second, the scientific personnel split their time fairly evenly between the lab and office. With these considerations in mind, a split-level approach to lab and office adjacency affords both colocation of analytical staff with other groups in the office area and only a half-level separation between analytical-lab operations and both office areas. Located on the middle-lab level, there is direct visual connectivity between all office functions and the analytical lab.

6. Planning for the unknown

Most analytical-testing functions have limited insight beyond what compounds or materials they currently handle, but likely need to plan for the unknown. With the market calling for aggressive treatments and the corresponding compounds in the pipeline, highly potent materials are likely to cross the lab threshold. These facilities need to be equipped (or quickly retrofitted) to safely handle them. The facility design must accommodate these future requirements with preplanned infrastructure and future spatial functionality.

The right balance between increased installation cost, preplanned infrastructure, and elongated downtime comes from detailed discussions during planning/programming. Conversations should cover classifications and quantities of materials, alternate forms of testing, and future instrument and equipment purchases. Equipping the lab on day 1 with ante rooms, advanced filtration, segregated exhausts, washable surfaces, misting showers, or other components is likely not the right answer. Ignoring potential future needs could result in significant renovations and downtime of the lab when the need arises. Installing a limited amount of infrastructure (HVAC, electrical) and preplanning some future floor space (ante rooms, isolators) is a wise yet minimal investment to be pre-positioned for the future.

-Brian Peasley is the science+technology core team leader at CRB's Philadelphia office. This article originally appeared on www.crbusa.com. CRB is a CFE Media content partner.



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
integrated building networks, NFPA 99, recover waste heat, chilled water systems, Internet of Things, BAS controls
40 Under 40; Performance-based design; Clean agent fire suppression; NFPA 92; Future of commissioning; Successful project management principles
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me