Food Manufacturer Wraps Up Piping Problem

Recurring cold-pipe condensation issues at Devro-Teepak's South Carolina facility have led facility managers to an absorbing solution.Devro-Teepak produces casings for the food industry, with the South Carolina facility manufacturing edible collagen sausage casings. In order to prevent deterioration, some materials must be cooled with a chilled-water system that operates at approximately ...

10/01/2001


Recurring cold-pipe condensation issues at Devro-Teepak's South Carolina facility have led facility managers to an absorbing solution.

Devro-Teepak produces casings for the food industry, with the South Carolina facility manufacturing edible collagen sausage casings. In order to prevent deterioration, some materials must be cooled with a chilled-water system that operates at approximately 44°F supply and 52°F return temperatures.

The hot South Carolina summers—which feature high temperatures typically combined with 90% relative humidity—create a perfect environment for condensation on this chilled-water piping.

"Despite the use of elastomeric pipe insulation, condensation on the chilled water pipes had been a problem since the plant was built in 1976," says Bob McCloskey, engineer with Devro-Teepak.

Two years ago, 75 feet of a new type of piping insulation was installed on two 6-in. chilled-water lines, then covered with PVC jacketing. According to McCloskey, the difference has been obvious.

The pipe insulation makes use of a hydrophilic wicking cloth, which is designed to continuously remove above-freezing water vapor that tries to condense on cold piping. As water vapor migrates through the insulation vapor retarder and condenses, it is captured by this super-absorbent cloth. The cloth then pulls the moisture to the underside of the system where it evaporates, leaving the pipe insulation dry and its thermal qualities intact.

"Even at the height of what we call 'drip season' during the summer, there have been no condensation problems on these sections of the pipe," says McCloskey. "The floor is dry under these sections, but wet under the elastomeric sections."

After observing the success of the pipe insulation, plant managers decided the test the cloth insulation on the plant's chiller units. Now, according to McCloskey, of the four units they have, only the one unit with insulation has no puddle of water beneath it.





No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
integrated building networks, NFPA 99, recover waste heat, chilled water systems, Internet of Things, BAS controls
40 Under 40; Performance-based design; Clean agent fire suppression; NFPA 92; Future of commissioning; Successful project management principles
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me