Engineering systems in manufacturing, industrial buildings: HVAC systems

Manufacturing and industrial facilities have some unusual engineering requirements, especially air handling, power needs, and fire/life safety systems. Air movement and air quality issues are discussed.

06/24/2013


Jonathan Eisenberg, PE, Associate Manager, Rolf Jensen & Associates Inc., Boston. Courtesy: Rolf Jensen & AssociatesBrian P. Martin, PE, PDX Electrical Discipline Manager, CH2M Hill, Portland, Ore. Courtesy: CH2M HillPeter Pobjoy, PE, LEED AP, Chief Design Officer, Southland Industries, Los Angeles. Courtesy: Southland IndustriesPeter Zak, PE, Principal, GRAEF USA, Milwaukee. Courtesy: GRAEF USA

Participants

Jonathan Eisenberg, PE, Associate Manager, Rolf Jensen & Associates Inc., Boston

Brian P. Martin, PE, PDX Electrical Discipline Manager, CH2M Hill, Portland, Ore.

Peter Pobjoy, PE, LEED AP, Chief Design Officer, Southland Industries, Los Angeles

Peter Zak, PE, Principal, GRAEF USA, Milwaukee  


CSE: What unusual requirements do HVAC systems for these facilities have that you wouldn’t encounter on other structures? 

Zak: Selection of HVAC systems is based on ventilation requirements, process needs, and budgets. 

Eisenberg: We often have a need for dedicated exhaust systems from more hazardous areas of a facility, which creates a need for additional shaft space in some cases. Also, in order to maintain the fire separation of the occupancy being ventilated, the dedicated exhaust ducts have to be enclosed in fire resistance rated construction. This is in lieu of installing fire dampers, which are prohibited in hazardous exhaust.

CSE: What unique solutions in HVAC systems or air movement have you specified recently? What “unusual” HVAC systems have you offered as an option to clients?

Pobjoy: Heat recovery is very important in buildings, especially where large quantities of outside air are used. We have recently used large enthalpy wheels for energy recovery in humid climates where we preconditioned 100% of the outside air entering the building both in the heating and cooling mode. In terms of air distribution, we have successfully used displacement ventilation by integrating the air supply into the building structure. 

Eisenberg: We worked on a large pharmaceutical plant that needed to partially recirculate the ventilation for a flammable liquid processing area, due to FDA regulations. We determined this practice to be acceptable, with organic vapor detection and an interlock to go to 100% outside air in the event of a spill or vapor release. 

Zak: The most common and cost effective have been air turnover units. These seem to work well in large open facilities and do not obstruct any other head operations such as cranes.



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Emergency lighting; NFPA 3 and 4; Integrated building systems; Smart lighting, HVAC design
Designing for energy efficiency; Understanding and applying NFPA 101 for mission critical facilities; Integrating commissioning and testing for fire alarm systems; Optimizing unitary pumping solutions
Economics of HVAC systems; NFPA 110-2016; Designing and choosing modular data centers
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
Driving motor efficiency; Preventing Arc Flash in mission critical facilities; Integrating alternative power and existing electrical systems
Putting COPS into context; Designing medium-voltage electrical systems; Planning and designing resilient, efficient data centers; The nine steps of designing generator fuel systems
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
click me