Engineering in K-12 schools: HVAC systems

03/17/2014


CSE: Do you find it more challenging to retrofit HVAC systems on older buildings than installing on new?

Najafi: Existing facilities do pose a retrofit challenge that adds another level of complexity compared to new building design, especially in the arena of coordinating with limited passageways (for equipment replacement) and hidden obstructions, but there are advantages that can be employed with some of these older, mass-based school structures that support lower differential temperature approaches, such as in radiant heating and cooling.

Hedman: Retrofitting older buildings is more challenging due to the existing structure. Systems in older schools were mostly designed for heating and ventilation only. Schools that are being retrofitted are now designed to incorporate air conditioning throughout. Existing ductwork cannot be used because it was sized for lower airflows (based on heating load) and not necessarily insulated. Therefore, as a design engineer on a retrofit project, we need to coordinate with the existing structure and architecture to incorporate larger ductwork.

Jefferson: Dealing with existing space limitations in older buildings can be a challenge. Too often though, designers don’t look at why it’s a challenge to retrofit these buildings. Most of these buildings didn’t use centralized, forced-air systems originally, so putting one in place today is going to create headaches. Instead, we look at the original design team’s approach, which typically involved steam or hot water piping (but no cooling). Thermodynamically, water or refrigerant is so much better than air for heat transfer, so we can move small piping around a building in much more compact spaces than what a ducted, air-based system would use. We still need to introduce ventilation air, but that system is usually much easier to accommodate than a centralized forced-air HVAC system.

Roy: It is almost always easier to design from a clean sheet than to try to integrate with existing systems. However, the relative ease isn’t necessarily a function of the building’s age. Many times, it’s easier to work with older buildings because they were built much more soundly and the existing MEP systems are generally much simpler. Whether gutting the existing and starting from scratch with an empty shell or retaining some or all of the existing systems, older (pre-1950s) systems are generally better documented, when original drawings are available, and it is easier to determine whether they are still viable or should be scrapped. Many times, there is greater pressure to reuse systems that are 1970s and 1980s vintage because they appear to be in functional condition, whether their operational efficiency justifies reuse or not. Most times, it is safe to say operation efficiencies trump functional conditions in determining whether to remove older systems. Also, code issues such as refrigeration availability and ozone depletion potential (ODP) calculations drive the elimination of older systems. However, project construction budgets many times require maintaining old, inefficient equipment. This is where the greatest challenges come up with retrofitting or renovating existing building systems: establishing capacity and condition, whether HVAC or electrical, when the budget doesn’t allow upgrading. Most times, it is easier to determine the capacity and condition of existing HVAC than existing electrical infrastructure. However, the challenge is always the same to establish the condition of concealed distribution systems like ductwork, piping, conduit, and wiring. If these distribution systems have to remain, they limit design options to less than optimal solutions.

Hammelman: It is more of a challenge to retrofit HVAC systems within older facilities, especially those built between 1950 and 1980, over retrofitting newer buildings. Often the buildings were not planned or designed to account for air conditioning, and now owners want to incorporate it. These facilities also possess environmental issues ranging from asbestos-containing materials to lead paint, which need to be remediated prior to construction, or they may not have adequate/existing electrical infrastructure and structural capacity to support the new HVAC equipment without significant upgrades and additional costs.


<< First < Previous 1 2 3 Next > Last >>

Anonymous , 04/07/14 11:10 AM:

Have any of you gentleman considered UFAD Under Floor Air Distribution to any of your school systems. Yes raised access floors must be used, but there are pluses on our side of the table. A number of engineers have successful projects, where these systems are more than adequate. I have answers for auditorium and rooms as well. As many of you know, noise in the classroom is failing students. Any student beyond the second row is only hearing about + 3db and those beyond the second row hear little of what the teacher is saying. This is based on students hearing 100% of what the teacher is saying. Want to learn how? Please call me at 704 489 1871
RICHARD , NC, United States, 08/19/14 08:23 AM:

Have You Gentlemen, ever thought of using Under Floor Air Distribution (UFAD)in schools? There is a lot of data of UFAD use in Colorado which may be helpful for you in the future. What is UFAD? It is a systems which utilizes raised access floors (not for gymnasiums) where the air becomes and integral part of the HVAC system. You have a pressurized system blowing cool air into the plenum and exiting thru special diffusers, which become part of the solution. Where the air comes from the floor and passes through only 6 ft of space where the occupants reside and continues as the air warms up and exits high at the roof? If you would like to learn more, please contact me. Have a nice day and what a wonderful project, as you fellows did it right....Richard Craig
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Designing for energy efficiency; Understanding and applying NFPA 101 for mission critical facilities; Integrating commissioning and testing for fire alarm systems; Optimizing unitary pumping solutions
Economics of HVAC systems; NFPA 110-2016; Designing and choosing modular data centers
Combined heat and power; Assessing replacement of electrical systems; Energy codes and lighting; Salary Survey; Fan efficiency
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
Driving motor efficiency; Preventing Arc Flash in mission critical facilities; Integrating alternative power and existing electrical systems
Putting COPS into context; Designing medium-voltage electrical systems; Planning and designing resilient, efficient data centers; The nine steps of designing generator fuel systems
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
click me