Electrical codes and standards within healthcare

Essential systems include emergency systems and equipment systems, which are crucial to life safety and patient care.

07/14/2017


Essential systems include emergency systems and equipment systems, which are crucial to life safety and patient care. Courtesy: RTM Engineering

When working with a facility's equipment system, it is crucial to understand how it supports the major electrical equipment necessary for basic facility operation and patient care. Essential systems include emergency systems and equipment systems-the emergency system is limited to circuits that are essential to life safety and crucial patient care. These are named the life safety branch and the critical branch.

  • The life safety branch of the emergency system supplies power to lighting, receptacles and equipment—such as illumination of means of egress and alarm and alerting systems—to provide adequate power needs to ensure patient and personnel safety. Additionally, HVAC controls are on the life safety branch as HVAC operations can impact smoke control and life safety.
  • The critical branch of the emergency power supplies power for task illumination, fixed equipment, selected receptacles, and special power circuits serving certain functions and areas—such as nurse call systems and blood, bone and tissue banks—related to patient care. This branch is intended to serve a limited number of locations to reduce the load and minimize the chances of a fault condition.

Here are a few National Fire Protection Association (NFPA) documents that address primary issues related to emergency power for hospitals include:

  1. NFPA 99, Healthcare Facilities – establishes criteria for levels of healthcare services or systems based on risk to the patients, staff, or visitors in health care facilities to minimize the hazards of fire, explosion, and electricity.
  2. NFPA 110, Emergency and Standby Power Systems – addresses installation, maintenance, operation, and testing requirements for emergency and standby power systems that provide an alternative source of electrical power in facilities if the normal electrical power source fails.
  3. NFPA 101, Life Safety Code – establishes strategies on how to protect people based on building construction, protection and occupancy features that minimize the effects of fire or other related hazards.

The location of each project determines which codes to follow. Healthcare facilities also need to adhere to State Department of Health requirements, which can vary from state to state.

- This article originally appeared on RTM Engineering blog. RTM Engineering is a CFE Media content partner.



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
integrated building networks, NFPA 99, recover waste heat, chilled water systems, Internet of Things, BAS controls
40 Under 40; Performance-based design; Clean agent fire suppression; NFPA 92; Future of commissioning; Successful project management principles
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me