District Department of Transportation
Existing building retrofit: District Department of Transportation; GPI/Greenman-Pedersen Inc.
Source: GPI/Greenman-Pedersen Inc.
Project name: District Department of Transportation
Location: Washington, D.C.
Firm name: GPI/Greenman-Pedersen Inc.
Project type, building type: Existing building retrofit, office
Project duration: 1 year
Project completion date: Sept. 29, 2007
Project budget for mechanical, electrical, plumbing, fire protection engineering only: $4.2 million
Engineering challenges
The project wanted to achieve U.S. Green Building Council LEED Silver certification, which required reduction of lighting energy consumption by 15% below the ASHRAE 90.1 2007 baseline.
Solutions
The lighting strategy used was to design the general ambient level to a maintained foot-candle average of approximately 30 foot-candles and provide LED task lights to raise foot-candle levels to 50 foot-candles per IES recommendations. LED exit signs specified further reduced energy consumption. Occupancy controls were used to control lighting throughout the space and reduce energy consumption. Wall-mounted infrared sensors controlled smaller enclosed spaces; ceiling-mounted ultrasonic sensors controlled corridors and open office spaces; ceiling-mounted dual-technology sensors (infrared and ultrasonic) controlled conference rooms; and wall-mounted dual relay infrared sensors controlled small conference rooms. All occupancy sensors were provided with either integral or external override off switches to allow users to turn off lights even when the room was occupied to improve energy savings. The project was awarded LEED ID+C Silver Certification.
Case Study Database
Get more exposure for your case study by uploading it to the Consulting-Specifying Engineer case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.
These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.
Click here to visit the Case Study Database and upload your case study.