Diagnostics for machine tool monitoring

An open modular architecture diagnostic system is designed for machine tool condition monitoring, as reported by Control Engineering Poland.

Krzysztof Pietrusewicz, PhD

11/23/2011


The control law in the synthesis of machine tool adaptive control systems (adaptive CNC systems) is determined by observing changes in the properties of the controlled process (milling or turning). These changes, if appropriately taken into account with a designed safety margin, enable a robust control algorithm to be created. The control system used for machine tool feed axes drives (as well as other subsystems) needs to be robust for machining quality and for safety.

Robustness issue

To achieve a constant high machining quality, the control systems should exhibit insensitivity to:

  • Variations in environmental conditions (vibrations, changes of temperature)
  • Variations in machining parameters (rate of travel composed of rates for individual axes, accelerations, travel profiles, etc.)
  • Nonlinearities of selected machine modules (friction, backlash)
  • Geometrical errors of the machine.

When designing a machine tool control system specifications include: machine kinematics (horizontal or vertical axes, dimensions of the machine), types of motors applied to feed drives (rotary or linear) and machining parameters, hence, motion parameters for individual axes axes (typical machining, high-speed machining, high-precision machining).

Specifications for control platform

The above-mentioned specifications determine requirements for hardware and software components of the control platform. These are:

  • The way the position/velocity is to be measured, as well as the measurement resolution and the desired accuracy

  • Communication protocols between the CNC processing unit and drive modules (for ‘typical’ machines it can be the CAN network, the MODBUS network, the nondeterministic Ethernet TCP/IP protocol to exchange data with the company office layer, or in the case of high-precision multi-axial applications it can be only the real-time industrial Ethernet: EtherCAT, Ethernet Powerlink, SERCOS, EtherNet/IP, Profinet or MODBUS-IDA),

  • Software architecture for sampling times, real-time operation including the way computations are to be allocated between many processor cores or processors themselves operating sometimes in the network, degree of advancement of control algorithms to be used in view of the designed precision level, the degree the machine tool operation monitoring and active supporting are to be integrated, hardware/software fusion concerning information from additional sensors.

Integration

The new approach within the open architecture CNC systems is the integration of the condition monitoring sub functionalities within the system. The main idea is to shorten the information roads (as well as to introduce the sensor fusion) between the CNC components to enable new possibilities for constant high quality assurance during machining.

 

Figure shows future open architecture CNC system modules, a project of Centre of Mechatronics WPU of Tech., Szczecin, with support from Polish Ministry of Science and Higher Education.  Courtesy: Control Engineering Poland

 

Figure above shows future open architecture CNC system modules. Typically motion control subsystem communicates with graphical user interface as well as with additional diagnostic modules through the tasks within the CNC RTOS (Real-Time Operating System) kernel (1). With the presented approach integration between the condition monitoring system is made on the basis of direct throughput of diagnostic modules computations and the motion control subsystem (2). This approach is the main idea of the Polish Ministry of Science and Higher Education grant no. N N502 336936 (acronym M.A.R.I.N.E. – multivariable hybrid ModulAR motIon coNtrollEr), conducted in close cooperation with one of the Polish machine tool builders.

 

Prototyping and testing of new hardware-software condition monitoring modules and possibilities of its integration within the open architecture CNC system is one of the goals of the research team of Centre of Mechatronics WPU of Technology, Szczecin. At now it is possible while the equipment of team has extended with new high-end system, called SAGITTARIUS – ICM. Its software-hardware architecture is shown in figure below.

Figure 1: The main subsystems are of: measurement of vibrations and acoustic pressure/emission signals, temperature, vision signal analysis, precision analog measurements. The system is based on the National Instruments hardware and software components. NI LabVIEW 2011 environment lets rapidly implement already developed algorithms, and shorten the time to market of new solutions.

The system presented here is financed by the Polish Ministry of Science and Higher Education grant. The resulting system is an ancronym: SAGITTARIUS – ICM (univerSAl inteGrated open architecture diagnostIc sysTem for research on machine Tool dynAmics and micRo-electromechanIcal systems in USage for development of Integrated Condition Monitoring modules for CNCs). The effort enables the research group from Centre of Mechatronics at West Pomeranian University of Technology to tighten already close cooperation with machine tool builders in Poland and other countries. It will formulate the fundaments for future development of integrated condition monitoring modules for CNCs. The team will propose a family of simple condition monitoring modules and set of rules for its integration for the interested companies within next five years.

Krzysztof Pietrusewicz, PhD is with the West Pomeranian University of Technology, Szczecin, Faculty of Electrical Engineering. He is also editor for Control Engineering Poland. His research work is connected with robust open architecture control and integrated condition monitoring approach for machine tool. This article appeared in the October Control Engineering North American edition's Control Engineering International page.

ONLINE extra - Additional information not include in the print version is included in this online version, above.

See the machine control channel at

controleng.com/machinecontrol



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Integrating lighting, HVAC systems, Energy codes and lighting, BIM and fire protection engineering
Engineering hospital electrical systems, Boilers and boiler systems, Building envelope best practices
Hospital indoor air quality, ASHRAE 90.1 update, Specifying piping materials, Integrated project delivery
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Consulting-Specifying Engineer case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Estimating data center PUE, Design tips for cost savings, Networked controls, NFPA 70E
Preventing arc flash, Backup power fuel choices, power for high-tech facilities
Using BIM in electrical power design; Closed-transition transfer; Medium-voltage distribution; Diesel emission regulations; Increasing emergency power capacity

Poll of the Week

When engineering systems in military buildings, what’s the most difficult issue you face?
Automation and controls
Codes and standards
Electrical and power
Energy efficiency, sustainability
Fire and life safety
HVAC


Click Here for Poll Archives
Sponsored by:

About Us | Contact Us | Advertise | Subscribe to Magazine | Site Map | Privacy Policy
Home | Channels | New Products | Media Library | Connect | Industry News | Events and Awards | Newsletters | Blogs | Magazine
Control Engineering | Plant Engineering | Consulting-Specifying Engineer
All content copyright © 2010-2013 CFE Media. All rights reserved.