Desiccant dehumidification for surgical rooms

Some surgical rooms can tolerate no more than +/- 2% change in relative humidity; desiccant dehumidifiers can be used as standalone solutions.

Source: Munters

03/24/2011


A newly constructed medical facility planned to offer patients corneal refractive (Lasik) surgery by reshaping the cornea with state-of-the-art equipment. But shortly after the facility was completed, surgical procedures were suspended abruptly. The existing HVAC system serving the surgical procedure room couldn’t deliver the required temperature and humidity necessary for optimal surgical outcomes.

Studies have shown that successful refractive surgeries demand exacting environments. That means no more than a +/- 1 F swing in temperature and a +/- 2% change in relative humidity (rh) over a 10-min period. It was a non-negotiable issue for surgeons who monitor digital readings of room temperature and humidity during every procedure. If the room doesn’t hold conditions, surgery cannot be performed.  As a result, the new surgical suite was temporarily unusable, and surgical procedures had to be performed offsite.

“Everyone was, to say the least, very disappointed,” the medical center’s facility manager said. “This was meant to be a showcase piece among surrounding hospitals.”

Obviously, the priority was to get the surgical facility up and running as soon as possible. Kroeschell Inc., a Chicago-based mechanical engineering firm, was chosen to evaluate and make recommendations to correct the problem.

According to Steve Cooper of Kroeschell, an investigation found that the existing chilled-water coil temperature did not allow for the discharge air temperature to be any lower than 50 F. This would not allow the space to be much below 50% rh, which was unacceptable because the required optimal conditions are 68 to 72 F and 40 to 45% rh.  There was an existing supplemental fan coil installed above the ceiling in the room, but even this unit could not effectively lower the relative humidity to acceptable levels.

“It was determined that mechanical dehumidification was needed to achieve the temperature and humidity criteria requested,” Cooper said. “The original equipment did not include dehumidification. In addition, highly accurate sensing instruments had to be included in the design.”

Stand-alone dehumidification

Kroeschell recommended a Munters HCD Series desiccant dehumidifier as a standalone solution to the problem. This unit incorporates Munters’ HoneyCombe wheel that is capable of collecting and releasing water six times every hour, 24/7. In addition to the desiccant wheel, the unit includes filtration, a supply fan, and a reactivation heater and discharge fan for wheel.

Fresh outdoor air comes into the dehumidification unit, which is controlled to maintain 43% rh discharge air humidity, and then enters the air handling unit serving the room. Room temperature and humidity sensors control the chilled-water coil valve, the electric duct heater, and the humidifier to maintain the design parameters. Air temperature and humidity sensors for air leaving the unit are incorporated into the programming logic of the existing direct digital control (DDC) system.

Though not ideal, the original air handler above the ceiling was kept in place because its removal would create dust in the surgical room, thereby causing problems with sensitive laser equipment in the room. Constant volume (CV) boxes were added to ensure a positive pressure in the room.

Achieving accuracy

The project was a success, with surgical procedures commencing immediately and continuing on schedule without interruption. Medical personnel report the system is maintaining humidity with a deviation of only +/- 0.6% rh, a tolerance they believe is virtually unprecedented in other Lasik surgery facilities in the country.

“We’re very proud of the outcome of this high-profile project,” Cooper said. “The Munters dehumidifier provided a straightforward, affordable solution for a facility with extraordinary requirements. This tells us the product has application possibilities wherever original chilled water design misses the mark in terms of latent load.”



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Integrating lighting, HVAC systems, Energy codes and lighting, BIM and fire protection engineering
Engineering hospital electrical systems, Boilers and boiler systems, Building envelope best practices
Hospital indoor air quality, ASHRAE 90.1 update, Specifying piping materials, Integrated project delivery
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Consulting-Specifying Engineer case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Estimating data center PUE, Design tips for cost savings, Networked controls, NFPA 70E
Preventing arc flash, Backup power fuel choices, power for high-tech facilities
Using BIM in electrical power design; Closed-transition transfer; Medium-voltage distribution; Diesel emission regulations; Increasing emergency power capacity

Poll of the Week

When engineering systems in military buildings, what’s the most difficult issue you face?
Automation and controls
Codes and standards
Electrical and power
Energy efficiency, sustainability
Fire and life safety
HVAC


Click Here for Poll Archives
Sponsored by:

About Us | Contact Us | Advertise | Subscribe to Magazine | Site Map | Privacy Policy
Home | Channels | New Products | Media Library | Connect | Industry News | Events and Awards | Newsletters | Blogs | Magazine
Control Engineering | Plant Engineering | Consulting-Specifying Engineer
All content copyright © 2010-2013 CFE Media. All rights reserved.