Controlling Condensation with the Right Insulation

Changes in one type of technology often make changes in related technologies necessary. For example, about a half-decade ago, facilities began running their chilled-water systems colder in an effort to reduce piping size and the required pumping power. While many engineers embraced this philosophy, it presented a new problem—condensation, especially in places like the southeastern United ...

06/01/2004


Changes in one type of technology often make changes in related technologies necessary.

For example, about a half-decade ago, facilities began running their chilled-water systems colder in an effort to reduce piping size and the required pumping power. While many engineers embraced this philosophy, it presented a new problem—condensation, especially in places like the southeastern United States. This condensation can lead to problems such as dripping, saturation of the insulation and mold growth.

Chuck Crim, Toledo, Ohio-based specification manager with Owens Corning, offers several suggestions. First, he stresses the importance of being familiar with the specific design criteria, temperature and relative humidity for the job location. "An engineer has got to know that they can't make assumptions that are incorrect, because if they specify a certain thickness based on an assumption and they're incorrect, they're going to have a problem," he says.

To elaborate, Crim explains that K values vary for different types of insulation. For example, fiberglass insulation has a K value of .23, while cellular glass has a K value of .33. As such, the thermal efficiency of an arbitrary insulation thickness—1.5 in., for example—will vary based on the type of insulation used.

Crim also stresses the need to understand the shortcomings of traditional methodologies, the danger of improperly installed joints and elbows and the possibility of damage to the jacket by other trades. "The insulator can go in there and do his job very well, and then you have a plumber or electrician who comes in and sticks his screwdriver in the insulation as a holder, and he's broken the vapor barrier." he explains.

Yet another issue to consider is whether the chilled-water system will be running prior to installation of the insulation. As insulation needs to be installed when the pipes are completely dry, the system must be shut down to allow any moisture to evaporate. This becomes a problem not only with retrofit projects, but also with new construction, as facility managers will often turn the system on to dry out the building prior to insulating. "And the question is, then, can you afford to shut the system down, dry the piping out, apply the insulation, then turn the system back on? In most cases, they either can't or won't do that," Crim says.

However, Crim points to an Owens Corning technology that can render these last two considerations irrelevant. Because moisture will almost always find some way to permeate insulation, the company developed VaporWick, a breathable, self-drying piping insulation system that allows the moisture to leave the area via a wick and evaporate into the ambient air, thus keeping the piping dry and factoring out condensation. As such, while the insulation uses a traditional fiberglass-based jacket, it doesn't rely on that jacket—or the installer's expertise.



Piping Insulation Suggestions

Be mindful of damage to insulation jacket by other trades

Familiarize yourself with a project location's design criteria, temperature and relative humidity

Don't select an arbitrary thickness; choose insulation thickness based on K value



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Economics of HVAC systems; NFPA 110-2016; Designing and choosing modular data centers
Combined heat and power; Assessing replacement of electrical systems; Energy codes and lighting; Salary Survey; Fan efficiency
Commissioning lighting control systems; 2016 Commissioning Giants; Design high-efficiency hot water systems for hospitals; Evaluating condensation and condensate
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
Driving motor efficiency; Preventing Arc Flash in mission critical facilities; Integrating alternative power and existing electrical systems
Putting COPS into context; Designing medium-voltage electrical systems; Planning and designing resilient, efficient data centers; The nine steps of designing generator fuel systems
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
click me