Understanding control valve bench set

02/01/1999


C ontrol valves are frequently reused, disassembled for maintenance, or 'stroke tested' before installation. A key factor to ensuring that control valves perform as expected, is understanding how operating conditions, changes in packing material, spring compression, and other influences contribute to overall control valve performance.

During control valve and actuator sizing, several factors must be considered to ensure the actuator can move and maintain the valve plug in place while operating at process conditions.

Factors influencing control valve performance under operating conditions include:

  • Diaphragm loading pressure , which is frequently 3-15 psi, but may be significantly higher, especially when a positioner is being used.

 

  • Diaphragm effective area is defined by the size of the actuator. Most manufacturers offer a variety of actuator sizes.

 

  • Valve plug stroke and travel is determined by sizing the valve body to meet flow requirements.

 

  • Secondary forces acting on the valve plug in order of importance include static unbalance, dynamic unbalance, packing friction, stem size, and diaphragm hysteresis.

 

  • Spring characteristics are the most active of all influences and should be determined after all other factors have been considered.

A control valve and actuator assembly is tested on a bench, not under actual operating conditions. To meet leakage criteria, the actuator must be assembled to provide seating force beyond that required to stroke the valves fully open (or closed). Bench set consist of considering all the factors and forces, selecting a spring with the correct spring rate, and setting an initial compression on the spring. The result is a control-valve assembly that responds differently when tested on the bench, than when it is installed in the process where all active forces are in effect.

Before reusing a control valve in a different application, mixing and matching valves and actuators, adding or removing a positioner, changing components that influence hysteresis, or adjusting spring compression, it is best to discuss the planned changes with the original valve manufacturer.



Comments?
E-mail dharrold@cahners.com





No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
40 Under 40; Performance-based design; Clean agent fire suppression; NFPA 92; Future of commissioning; Successful project management principles
BIM coordination; MEP projects; NFPA 13; Data center Q&A; Networked lighting controls; 2017 Product of the Year finalists
Emergency lighting; NFPA 3 and 4; Integrated building systems; Smart lighting, HVAC design
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
Tying a microgrid to the smart grid; Paralleling generator systems; Previewing NEC 2017 changes
Driving motor efficiency; Preventing Arc Flash in mission critical facilities; Integrating alternative power and existing electrical systems
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me