Three web server architectures aid plant-floor, enterprise integration

Driven by manufacturing's desire to connect the factory floor with the rest of the enterprise, web-enabled PLCs and Ethernet are giving users new ways to view and control factory data using embedded web servers. When selecting a web-enabled automation device, users can choose from three distinct system architectures.

Richard Baker

01/01/1970


Driven by manufacturing's desire to connect the factory floor with the rest of the enterprise, web-enabled PLCs and Ethernet are giving users new ways to view and control factory data using embedded web servers. When selecting a web-enabled automation device, users can choose from three distinct system architectures.

Each architecture's performance capabilities depend on the location of the web server within the system hardware. One architecture places a web server in the CPU of the PLC; a second installs a server on a separate board in the PLC backplane; and a third places it on a computer outside the PLC.

External web server

When installed in a separate computer, a web server must rely on a data collection process, which typically uses a network, such as Profibus or DeviceNet, to communicate with factory automation devices. This architecture usually employs an OPC/DDE server as the PLC interface. One advantage of this method is that users only need to buy several software components, but they can store many web pages on the PC's disk drives. Disadvantages include higher system costs and lower potential reliability due to additional components. Processing cycle time may be slower because two separate networks are being used.

Backplane-based server

A web server on a PLC's backplane is typically placed on an Ethernet board, executing on the same CPU with the TCP/IP stacks. Several processors can perform this task. Some of the best choices range from a lower-cost 80186 to Motorola's 860T for higher performance implementations. The Ethernet board requires at least 1 MB of flash RAM to store a few simple web pages, and many tens of megabytes for applications containing complex pages.

For example, Schneider Electric Automation's (North Andover, Mass.) first Web-enabled PLC uses an Ethernet board that provides high performance and allows users to load complicated web pages. Its CPU is a 40-MHz 860T Ethernet CPU with 16 MB of bursting SDRAM and 8 MB of flash ROM. Memory access is optimized to limit wait states and memory access delays. It also incorporates 100-Mbps Ethernet, both twisted pair and fiber, into the module.

Schneider's Web-enabled PLC also features an ultra-high-performance TCP/IP stack, which was developed to work in parallel with the standard stack for high-speed cyclic I/O scanning. To handle access to PLC data, the Web-enabled PLC includes a set of Java beans to collect data from the PLC and help create displays that improve flexibility and access. It allows users to create almost any HMI with a web browser, eliminating the need for expensive software packages.

Another advantage of backplane-based web server architecture is that its high-speed access to the PLC across the backplane doesn't impact PLC performance. The separate board provides space on board memory supporting several complex web pages.

Server on CPU

The third architecture puts a web server directly on the PLC's CPU. This solution is less costly because it eliminates the need for a separate board and CPU. However, it requires significant innovation to maintain determinism and proper PLC performance, while also managing TCP/IP stacks and the web server.

Schneider uses this approach in a second Web-enabled PLC with a board designed for fast memory timing, so the CPU isn't delayed by waiting for memory access. This PLC places an Ethernet stack and HTTP server in a PLC without impacting determinism of the logic solving function. Memory is limited to 512 K SRAM and 256 K flash RAM due to the chip's addressing limitations. The board's size is limited by the PLC's form factor, which requires the board to fit in a 4.75 x 2-in. space.

Today, users are implementing applications with varying size, complexity, and performance requirements, as well as related web pages. Fortunately, these three web server architectures can help implement a solution that best meets their needs.

For related suppliers go to www.controleng.com/buyersguide; for more info, circle 368 at www.controleng.com/freeinfo.

Richard Baker led the Schneider Electric Automation (North Andover, Mass.) design engineering team that developed its Web-enabled PLC.



A

Web server architectures

PC with web browser

Ethernet

Web server on personal computer

Data collection task (OPC/DDE)

Industrial network

PLC

B

PC with web browser

Ethernet

Ethernet board with web server

PLC

C

PC with web browser

Ethernet

PLC with Ethernet and web server running on PLC CPU

Source: Control Engineering with data from Schneider Electric Automation



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
40 under 40
Integrating lighting, HVAC systems; Use building energy modeling software to balance lighting and HVAC systems
Engineering hospital electrical systems, Boilers and boiler systems, Building envelope best practices
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Consulting-Specifying Engineer case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Estimating data center PUE, Design tips for cost savings, Networked controls, NFPA 70E
Preventing arc flash, Backup power fuel choices, power for high-tech facilities
Using BIM in electrical power design; Closed-transition transfer; Medium-voltage distribution; Diesel emission regulations; Increasing emergency power capacity
About Us | Contact Us | Advertise | Subscribe to Magazine | Site Map | Privacy Policy
Home | Channels | New Products | Media Library | Connect | Industry News | Events and Awards | Newsletters | Blogs | Magazine
Control Engineering | Plant Engineering | Consulting-Specifying Engineer
All content copyright © 2010-2013 CFE Media. All rights reserved.