Project profile: Improving switchgear inspections at London's Stansted Airport

In this project profile, Lonsdon Stansted Airport Engineering Team performed an existing building retrofit in order to reduce the amount of time needed for maintenance inspections.

03/20/2014


Project name: Improving Switchgear Inspections at London's Stansted Airport

Project type: Existing building retrofit

Engineering Firm: London Stansted Airport Engineering Team

Building type: Utilities/public works/transportation

Location: Stansted, Essex, United Kingdom

Timeline: Nov. 11, 2012 - Dec. 24, 2012


Thermographer inspects switchgear at Stansted Airport through an IRISS CAP infrared camera. Courtesy: London Stansted Airport

Building details

London Stansted Airport has permission to handle 35 million passengers annually and currently 17.5 million people pass through the terminal building each year. The airports electrical structure is enormous. Power is brought onto the site at 33kV and transformed down to 11V. 

Project details

At best, Stansted's engineers had four hours per night in which to conduct predictive maintenance inspections. By the time they had the system safe, the window of opportunity was reduced even more. This meant the entire inspection cycle was significantly protracted and no system could be checked under load. With the installation of IRISS CAP Series infrared inspection windows, the savings in terms of inspection time and associated costs went up dramatically. Payback was instant, but the benefits extended beyond that.

With IRISS infrared windows, Stansted Airport switchgear systems are thoroughly inspected. Courtesy: London Stansted Airport

Project success

Once the IRISS windows were installed there was an immediate impact on switchgear inspections time. It took just took five hours to complete the job in daylight hours, including walking from one substation to the next and coffee breaks. Previously, it took the engineers two nights to inspect just one panel. There is no longer a need for isolations or back feed, and the engineers' safety is completely assured. A single thermographer with a thermal imaging camera and without PPE can do everything. An initial thermal survey of the fully energized low-voltage systems that serve the main terminal block showed just two minor cable faults. For the first time, the airport had a benchmark for trending future performance and the complete assurance that everything was working optimally. This was not possible before install the IRISS CAP Series IR window.


London Stansted Airport, Enterprise House, Bassingbourn Road, Essex, United Kingdom CM24 1QW



Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Boiler basics; 2017 Product of the Year winners; Manufacturing facilities Q&A; Building integration; Piping and pumping systems
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Boiler basics; 2017 Product of the Year winners; Manufacturing facilities Q&A; Building integration; Piping and pumping systems
2017 MEP Giants; Mergers and acquisitions report; ASHRAE 62.1; LEED v4 updates and tips; Understanding overcurrent protection
Integrating electrical and HVAC for energy efficiency; Mixed-use buildings; ASHRAE 90.4; Wireless fire alarms assessment and challenges
Power system design for high-performance buildings; mitigating arc flash hazards
Transformers; Electrical system design; Selecting and sizing transformers; Grounded and ungrounded system design, Paralleling generator systems
Commissioning electrical systems; Designing emergency and standby generator systems; VFDs in high-performance buildings
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.
Automation Engineer; Wood Group
System Integrator; Cross Integrated Systems Group
Fire & Life Safety Engineer; Technip USA Inc.
This course focuses on climate analysis, appropriateness of cooling system selection, and combining cooling systems.
This course will help identify and reveal electrical hazards and identify the solutions to implementing and maintaining a safe work environment.
This course explains how maintaining power and communication systems through emergency power-generation systems is critical.
click me