HP's newest data center opens with a unique cooling set up

In northeast England, HP's Wynyard Center opened this week with a unique cooling set up and an innovative design.


According to DatacenterDynamics , the HP Wynyard data center opened this week in northeast England. Contrary to the reports, the data center site will not be cooled by the wind. What will be cooled is filtered outside air.

What separates it from other mega scale data center sis the sign, which will see large volumes of slow moving air sucked in using 6.88-ft variable speed axial fans that service each data halls-there are four data halls currently available; one is live, one is being commissioned, and remaining two will take load later this year.

The eight inlet fans per data hall move the air through bag filters to a 16.4-ft sub-floor pressurized plenum. The air is then forced upwards through cold aisle contained cubes before passing through servers, being drawn out through the ceiling, and then re-circulated.

Eight exhaust fans draw the air out and pass it back over the data halls where it is mixed with outside air or where it can be fully re-circulated. Chiller capacity is available to augment the cooling when necessary and the chillers are also operated 200 hours/year to provide humidification.

To view the data center's floor plan, system configurations, and other diagrams, visit the DatacenterDynamics website here .

No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
Salary survey: How much are you worth?; Dedicated outdoor air systems; Energy models and lighting
Fire, life safety in schools; Fire protection codes; Detection, suppression, and notification; 2015 Commissioning Giants; Emergency and standby power in hospitals
HVAC and building envelope: Efficient, effective systems; Designing fire sprinkler systems; Wireless controls in buildings; 2015 Product of the Year winners
Designing positive-energy buildings; Ensuring power quality; Complying with NFPA 110; Minimizing arc flash hazards
Implementing microgrids: Controlling campus power generation; Understanding cogeneration systems; Evaluating UPS system efficiency; Driving data center PUE, efficiency
Optimizing genset sizing; How the Internet of Things affects the data center; Increasing transformer efficiency; Standby vs. emergency power in mission critical facilities
As brand protection manager for Eaton’s Electrical Sector, Tom Grace oversees counterfeit awareness...
Amara Rozgus is chief editor and content manager of Consulting-Specifier Engineer magazine.
IEEE power industry experts bring their combined experience in the electrical power industry...
Michael Heinsdorf, P.E., LEED AP, CDT is an Engineering Specification Writer at ARCOM MasterSpec.