Designing office space: Electrical, power systems

Office building clients demand sustainability, flexibility, and cost conservation in both new and existing buildings.

10/22/2012


Michael F. Cooper, PE, LEED AP, is a Managing Principal at Harley Ellis Devereaux in Southfield, Mich. Courtesy: Harvey Ellis DevereauxKurt Karnatz, PE, CEM, LEED AP, HBDP, HFDP, is the President of Environmental Systems Design Inc. (ESD) in Chicago. Courtesy: ESDKent W. Peterson, PE, FASHRAE, LEED AP BD+C, BEAP is the Vice President/Chief Engineer of P2S Engineering Inc. in Long Beach, Calif. Courtesy: P2S Engineering

Respondents

Michael F. Cooper, PE, LEED AP, Managing Principal, Harley Ellis Devereaux, Southfield, Mich.

Kurt Karnatz, PE, CEM, LEED AP, HBDP, HFDP, President, Environmental Systems Design Inc., Chicago

Kent W. Peterson, PE, FASHRAE, LEED AP BD+C, BEAP, Vice President/Chief Engineer, P2S Engineering Inc., Long Beach, Calif. 


CSE: What’s the one factor most commonly overlooked in electrical systems? 

Cooper: The most overlooked element in electrical systems is planning for the future. We know that once these systems are installed, it’s costly and disruptive to modify or expand them. We also know that changing tenant needs are driving the need for system adaptability. Information technology alone has driven significant changes in electrical systems design. It’s critical that time is taken at the start of each project to assess the needs of today and tomorrow and how today’s systems can help facilitate future growth. 

Karnatz: Power quality. While the total power required on a W/sq ft basis is trending down for office occupancy, the need for power quality and reliability is not. 

CSE: Describe a recent project in which you had complex metering and submetering in a building. 

Karnatz: As previously mentioned, large office buildings with multiple and diverse occupancy needs very often require complex metering schemes. In buildings where there is a great diversity in tenancy and therefore infrastructure consumption, the need to accurately allocate use costs is very important. Very often buildings have some tenants that might consume three to five times the amount of power and cooling that others consume. 

Cooper: One recent project, which achieved a U.S. Green Building Council LEED Platinum Certification, included a building distribution system segregated by load type as well as metering at each tier of the system to for real-time monitoring and management. “Dashboard” displays throughout the facility indicate real-time usage and trending of all utility services. There is truth in the statement, “what gets measured, gets managed.” 

CSE: How do you balance the need for reliable power with the desire for efficiency and sustainability? 

Karnatz: We believe that efficiency, sustainability, and reliability is the three-legged stool of power delivery in an office environment. Depending on tenant enterprise needs, the weighting of the importance of these three elements will vary. 

Cooper: Step one is to understand the level of reliability required by the owner. A computer facility may, for example, have a different need than a general office environment. Once understood, we can then properly evaluate and design power system selective coordination such that impact to system efficiency or sustainability is minimized. The goal is to provide what’s needed in the most efficient way possible. 

CSE: What type of backup or standby power systems have you specified into an office building recently? 

Cooper: Most recently, we have installed parallel natural gas generators (N+1) with rotary UPS systems for critical electrical loads. As our reliance on information technology, Web-based communications, and data management continues to increase, the focus on robust electrical systems and reliable backup provisions will likewise increase. 

Karnatz: We commonly provide backup and standby power through the use of multiple utility feeds, supplementary power generation, and UPS systems. 



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
40 under 40
Integrating lighting, HVAC systems; Use building energy modeling software to balance lighting and HVAC systems
Engineering hospital electrical systems, Boilers and boiler systems, Building envelope best practices
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Consulting-Specifying Engineer case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Estimating data center PUE, Design tips for cost savings, Networked controls, NFPA 70E
Preventing arc flash, Backup power fuel choices, power for high-tech facilities
Using BIM in electrical power design; Closed-transition transfer; Medium-voltage distribution; Diesel emission regulations; Increasing emergency power capacity
About Us | Contact Us | Advertise | Subscribe to Magazine | Site Map | Privacy Policy
Home | Channels | New Products | Media Library | Connect | Industry News | Events and Awards | Newsletters | Blogs | Magazine
Control Engineering | Plant Engineering | Consulting-Specifying Engineer
All content copyright © 2010-2013 CFE Media. All rights reserved.