ASHRAE 135 addenda pass
BACnet adds language options for both computers and humans.
Source: ASHRAE
At ASHRAE's 2010 Winter Conference held recently in Orlando, the BACnet committee celebrated the approval for final publication of eight addenda to the ANSI/ASHRAE Standard 135, A Data Communication Protocol for Building Automation and Control Networks .
The addenda are expected to be available on ASHRAE.org by the end of February.
The addenda include a specification for a standard way of representing data in XML that will give BACnet new capabilities for communications between a wide range of applications. The Extensible Markup Language (XML) is a popular technology in the data processing and communications worlds due to its capability to model complex data and its flexibility to be transformed and extended.
The XML syntax is intended to be the core data representation for a variety of uses:
• Powerful new Web services that are capable of efficient exchange of complex structured data.
• An electronic version of a BACnet PICS document, consumable by workstations and other tools, to describe the capabilities of a device.
• An "as built" description of a deployed device, distributed either as a separate file or as a BACnet File object resident in the device itself.
• Descriptions of proprietary objects, properties and data types, which may be simple, for basic data sharing purposes, or extremely rich, providing complete descriptions of the meaning and usage of the data in multiple human languages.
• An export/import format for tools and workstations publish their knowledge of a complete system of devices and networks.
• An XML version of an EPICS, including the complete test database and other test-oriented data.
In addition to the new "computer language" of XML, another addendum has added an important new capability for human languages as well. When the Unicode character set was created many years ago, it was constructed to be universal set of characters to support most of the world's languages together in one stream. However, its original 2-byte encoding caused trouble with a lot of existing systems that were designed to process only the 1-byte characters common in western languages. The "UTF-8" encoding was created to solve this problem and quickly became a very popular method of conveying international text on the World Wide Web. BACnet has also embraced this standard and uses it in a way that fully takes advantage of its compatibility with the existing and ubiquitous ANSI/ASCII character set.
BACnet has also added support for more data types as well. A set of new "Value" objects rounds out BACnet's ability to represent different data types in a uniform and standard way. Added to the original Analog, Binary and Multi State Value objects, are new Value objects for every primitive datatype that BACnet supports, including support for character strings and large numerics.
Case Study Database
Get more exposure for your case study by uploading it to the Consulting-Specifying Engineer case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.
These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.