Advancing Technology: High-efficiency gas turbines

General Electric and Siemens are among companies pushing the frontiers of large high-efficiency gas turbines for electricity generation. Target is more than 60% thermal efficiency for combined-cycle power plants.

Frank J. Bartos, PE

11/08/2010


Introduction of the newest H-class gas turbines over the past few years is making greater than 60% thermal efficiency a reality for combined-cycle gas turbine (CCGT) power plants. H-class is the largest and most efficient of gas turbines now being produced for electric power generation.

Relatively few manufacturers build these giant machines; among them are Alstom, General Electric, Mitsubishi Heavy Industries, and Siemens. In the forefront of H-class gas turbine development, GE Energy has three installations worldwide at CCGT power plants. GE’s first H-class installation was a 9H system that began service in 2003 at Baglan Bay power station in Wales, U.K. This 520-megawatt (MW) output, 50-Hz system has compiled more than 36,000 operating hours and served as a technology validation site.

Three other 50-Hz GE H-turbine systems are at work in Japan at Tokyo Electric Power Co.’s (TEPCO) Futtsu thermal power station 4. The first system went into service in 2008, while the third one just recently entered commercial operation. “That brings the total H-technology output for three units at the TEPCO site to 1,520 MW,” said Don Hoffmann, advanced combined cycle platform leader, GE Power & Water. A noteworthy sidelight is that Futtsu 4 is part of a larger TEPCO complex that produces more than five gigawatts of power—making it one of the world’s largest gas turbine combined-cycle installations. Besides the three H systems, the site employs 18 smaller GE gas turbines.

GE’s first 60-Hz H system went online in 2008 at Inland Empire Energy Center in Riverside County, CA, accumulating more than 8,000 operating hours. With the recent start-up of a second turbine, the plant has surpassed 10,000 total operating hours, according to Hoffmann. Inland CCGT power plant has maximum net rated electric output of 775 MW.

Modular implementation

Meanwhile, Siemens Energy is approaching completion of a 10-year development program for its 50-Hz H-class SGT5-8000H turbine that weighs in at 440 metric tons and is designed for 530 MW output in combined-cycle operation. Siemens chose a novel, modular commercialization approach by installing the turbine at a working gas power plant—Irsching 4, near Ingolstadt, Germany. Following synchronization to the grid in March 2008, extensive design validation, durability evaluation, and full-load testing in simple-cycle mode has taken place. Some 1,500 operating hours have been achieved in this mode.

In phase 2 of the program, build-out of the combined-cycle plant began, which included civil engineering work for cooling water piping and the heat recovery steam generator (HRSG), where hot turbine exhaust will be fed in combined-cycle operation. Other progress included installation or near completion of most of the steam turbine, condenser, cooling system, HRSG, and electrical and I&C equipment, explained Willibald Fischer, Siemens’ program manager for H-turbines. Fischer adds that most of the mechanical and electrical installation work will be completed by year-end 2010.

Hot recommissioning of the gas turbine and associated combined-cycle systems will follow early next year. “First firing is on schedule for early January 2011 and hand-over to our customer—E.ON Kraftwerke—remains on target for mid-2011,” said Fischer. “Based on final evaluation of hundreds of terabytes of test data, we are very confident to be able to demonstrate in reality what we promised.”

Scaled from its 50-Hz turbine, Siemens has designed a 60-Hz machine (SGT6-8000H) and announced a first sales order of six units in June 2010 (read more online).


Frank J. Bartos, PE, is a Control Engineering contributing content specialist. Reach him at braunbart(at)sbcglobal.net

 


Also see:http://www.controleng.com,%20search%20for%20/

 

- First order for Siemens’ 60-Hz, H-class gas turbine

 

- The hunt for 60+% thermal efficiency

 

- Largest gas turbine: 2,838 sensors, 90 GB data per hour of testing

 

- New, efficient industrial turbines coming



No comments
Consulting-Specifying Engineer's Product of the Year (POY) contest is the premier award for new products in the HVAC, fire, electrical, and...
Consulting-Specifying Engineer magazine is dedicated to encouraging and recognizing the most talented young individuals...
The MEP Giants program lists the top mechanical, electrical, plumbing, and fire protection engineering firms in the United States.
40 under 40
Integrating lighting, HVAC systems; Use building energy modeling software to balance lighting and HVAC systems
Engineering hospital electrical systems, Boilers and boiler systems, Building envelope best practices
Case Study Database

Case Study Database

Get more exposure for your case study by uploading it to the Consulting-Specifying Engineer case study database, where end-users can identify relevant solutions and explore what the experts are doing to effectively implement a variety of technology and productivity related projects.

These case studies provide examples of how knowledgeable solution providers have used technology, processes and people to create effective and successful implementations in real-world situations. Case studies can be completed by filling out a simple online form where you can outline the project title, abstract, and full story in 1500 words or less; upload photos, videos and a logo.

Click here to visit the Case Study Database and upload your case study.

Estimating data center PUE, Design tips for cost savings, Networked controls, NFPA 70E
Preventing arc flash, Backup power fuel choices, power for high-tech facilities
Using BIM in electrical power design; Closed-transition transfer; Medium-voltage distribution; Diesel emission regulations; Increasing emergency power capacity
About Us | Contact Us | Advertise | Subscribe to Magazine | Site Map | Privacy Policy
Home | Channels | New Products | Media Library | Connect | Industry News | Events and Awards | Newsletters | Blogs | Magazine
Control Engineering | Plant Engineering | Consulting-Specifying Engineer
All content copyright © 2010-2013 CFE Media. All rights reserved.