Damper tests provide valuable insights. Seriously--I'm not kidding. Part 1
Wayne Jin and I recently had a chance to test the flow versus
damper blade position characteristics for the AHU1 economizer
dampers at the Pacific Energy
Center (PEC). We discovered a few interesting
things, including that theory didn’t match reality, at least for
our test. Over the course of the next few posts, I’ll explore
the test Wayne and I performed, including the theory behind it and
the results. This post will give you some background
information and set the stage for subsequent discussions.
Wayne was one of the student’s in last year’s
hands-on retrocommissioning workshop series at the PEC. The top
photo below is a picture of the AHU we tested, along with the 2nd
group of folks to go through the PEC RCx class. The lower
photo is a picture of the unit’s economizer dampers. The
outdoor air dampers are the vertical sections and the return air
dampers are the horizontal section.


As you can see, they are showing signs of age, including
missing blade seals (note the gap at the top of
the outside-air dampers). The jamb seals are still in
place and serviceable. While these conditions may not be the
norm, I would not be surprised if many of you see dampers in
similar condition in many of the systems you are working on; I know
I do. As a result, you may find that the information that is
about to be presented can be extrapolated and applied to your
projects, especially if you are working to improve the performance
of existing buildings and their systems.
The goal of the test we performed on the AHU1 economizer dampers
included a number of targets:
- Understand how well the minimum position signal approach for
regulating minimum outdoor air flow that was in use at the PEC
worked. - Understand the implication of the missing damper blade seals in
terms of leakage at minimum and maximum outdoor air. - Characterize the damper performance in terms of flow vs. stroke
and compare it to the theoretical predictions.
The minimum outdoor air issue listed in the first bullet is the
original reason the class targeted the dampers as a
retrocommissioning (RCx) opportunity. Common wisdom is that
for a damper to be able to control flow in a system, it needs to
have a pressure drop that is significant relative to the system it
is controlling. Furthermore, the more significant the
damper’s pressure drop is, the more linear the relationship between
blade rotation and flow will be. These concepts are often
stated graphically in curves similar to the following, which are
pressure drop vs. flow performance for opposed and parallel blade
dampers with different ratio’s of damper pressure drop to system
pressure drop (the ratio is often called alpha).


These curves are published in a number of sources, including the
ASHRAE Handbook of Fundamentals Chapter 15, ASHRAE
Guideline 16 -
Selecting Outdoor, Return, and Relief Dampers for Air-Side
Economizer Systems and Powers Application Engineering Form
AE-24 - Damper Sizing and Selection (sorry, no link for this at
this time). The curves in the picture are reproduced in a
damper sizing spreadsheet that is Chapter 2, Section 2.4.3.2.
Component Specifications of the Control Design Guide, which
is a publicly available resource.
Damper pressure-drop is related to damper velocity and for most
HVAC systems a general rule of thumb is that the velocity through
the economizer dampers will need to be in the range of 1,500 to
2,500 feet per minute (fpm) to achieve an alpha that is
satisfactory in terms of providing a linear flow vs. stroke
characteristic. High alphas, which translate to oversized
dampers, will tend to provide a two position characteristic.
If you look at the opposed blade curve in the picture above, you
will notice that for an alpha of 200, 20% stroke provides nearly
50% flow. For a parallel blade damper under the same
conditions you would get 75% flow! Clearly, theory suggests
that an oversized outdoor air damper using a minimum position
signal strategy to control minimum outdoor air flow has the
potential to over-ventilate and thus, is a good target for a
retrocommissioning effort.
Come back in a few days and we’ll look at how the PEC
Retrocommissioning class used this theoretical data and rules of
thumb to assess the potetial for improving performance and saving
energy in the economizer serving AHU at the PEC.
Prertiesels commented:
Here you can find everything you need For real
stoonnalooppy commented:
Here you can find everything you need your ma to for test business song in king and in marilyn how to home who truck and and to For real
Channaexceerb commented:
Here you can find everything you need
lfc badge
solo kittens
1906 kaylor south dakota
lightup shift knobs
pac sun outlet in florida
instinct diet
college girl next door nude
earth day 2009 date
ink canon mp830
pregnant taking amoxicillin
tips for fast weight loss
bucks sixers 2001 playoffs officials
pump it up mp3s
chevolet of limrick
factor tree template
cartridge ink jet printer refill
fond du lac wi outlet mall
keygen for nwn diamond
propane conversion for 3 hp briggs and s
cross pen fountain
jcpenneyoutletstoremassachusetts
price of gold in 1995
effect of corrosion in oil and gas trans
lgbtq youth
cindy margolis
fleece cat ear hat patterns
linux citrix client 64 bit
macedonian body type
ashleigh kena boykins
hand painted baby gifts
darin bill silver
donney purse outlet
For real
sophiemarcaues commented:
Hello my name is Sophie, I\’m really new to all this, just got my computer and Internet. I want to start my own blog but I just don\’t know how to go about building my own web site, can anyone please recommend what would be a good start? like….do I have to learn programming to build my own web site? Or at least point me in the right direction or where exactly I should look for help? Thanks, and sorry for the off topic post! I just didn\’t know where else to ask…
AerobbyOner commented:
<!DOCTYPE html PUBLIC \”-//W3C//DTD HTML 3.2//EN\”>
<html>
<head>
<title></title>
</head>
<body>
jlo accaunt ugjaka
</body>
</html>
elutlegiomi commented:
<!DOCTYPE html PUBLIC \”-//W3C//DTD HTML 3.2//EN\”>
<html>
<head>
<title></title>
</head>
<body>
Funny URL www.csemag.com Glad to show you path to free for all cool
source. Make a note banners 1:1 exchange system for your needs.
</body>
</html>
Vanessa commented:
<!DOCTYPE html PUBLIC \”-//W3C//DTD HTML 3.2//EN\”>
<html>
<head>
<title></title>
</head>
<body>
male prostate milking video
</body>
</html>
kederenda commented:
Hey Guys My name is Admin I hope this is posted int he right section. I felt this was the best place to ask about this , if not please feel free to move it where it belongs, I really like this place and will be an advid poster here. Nancy
I have been into internet marketing lately and would like to know if you know anything about blackhat marketing techniques? The reason I ask is because I found a couple places where people have proof of making over $900 a day from some these Black hat methods. Im just curious if anyone here is making money online through Blackseo or any types of whitehat techniques like these sites are about.
These sites have many different money making free scripts and types of ways to make money online. Alot of it has to do with CPA and affiliate programs. Hopefully you guys could help me understand some of these methods or just PM me and I can show the methods I am struggling with and I would be willing to give the scripts I bought for free, if you can help me figure them out. I just want to make money online since the economy is so bad now.
Here is the first site Black hat forum
Here is the 2nd site Make Money Online
kederenda commented:
Whats Up My name is Admin I hope this is posted int he right section. I felt this was the best place to ask about this , if not please feel free to move it where it belongs, I really like this place and will be an advid poster here. Susan
I have been into internet marketing lately and would like to know if you know anything about blackhat marketing techniques? The reason I ask is because I found a couple places where people have proof of making over $900 a day from some these Black hat methods. Im just curious if anyone here is making money online through Blackseo or any types of whitehat techniques like these sites are about.
These sites have many different money making free scripts and types of ways to make money online. Alot of it has to do with CPA and affiliate programs. Hopefully you guys could help me understand some of these methods or just PM me and I can show the methods I am struggling with and I would be willing to give the scripts I bought for free, if you can help me figure them out. I just want to make money online since the economy is so bad now.
Here is the first site Blackhat seo
Here is the 2nd site Make Money Online
JokesFunnn commented:
<!DOCTYPE html PUBLIC \”-//W3C//DTD HTML 3.2//EN\”>
<html>
<head>
<title></title>
</head>
<body>
How can you tell when a lawyer is lying? His lips are moving.
</body>
</html>
Wayprorostago commented:
<!DOCTYPE html PUBLIC \”-//W3C//DTD HTML 3.2//EN\”>
<html>
<head>
<title></title>
</head>
<body>
I love your services and products, many thanks!
</body>
</html>
SonyaSunny commented:
Guruchel commented:
Bobi commented:
Rick commented:
Peter commented:
Mister commented:
Jak commented:
Guruchel commented:
Mister commented:
Vanessa commented: