Motor Optimization; Same Efficiency + Different Slip = Different Savings
August 18, 2008

In my previous post, I looked at using MotorMaster to take a life cycle cost perspective on the motor selection for a 5 hp chilled glycol pump serving an ice storage system. In doing that, I looked at upgrading from a Title 24/Energy Policy Act compliant motor to a premium efficiency motor as defined by NEMA. But, as you can see from the list below, there are a lot of choices, including motors with efficiencies that exceeds the NEMA definition of premium efficiency. 

The motors I contrasted previously are highlighted in green and yellow in the table above. In this post, I will take a look at some of the peak efficiency options, specifically, the ones highlighted in lavender and red. Since the steps used to to generate the results with MotorMaster are identical to what I described in the last post, I will not repeat them here and have simply summarized the results in the table below which has been color coded to match the motor selections in the table above.

When you first look at the table, you may conclude that I made a mistake and imposed a slightly larger load on the motor that is color coded in lavender (96.5% of full load versus the 95% of full load number used for the other selections) causing the savings projected for that selection to be lower than it should be. After all, why wouldn't two motors with virtually identical efficiencies deliver virtually identical savings? The answer lies in the difference between rated motor speeds (1,750 rpm in one case and 1,760 rpm in the other) and the fact that the motor is driving a centrifugal machine, in this case, a pump which will by its nature, do more work if you run it at a higher speed, all other things being equal.

The rated speed for the squirrel cage motors we use on our HVAC equipment is the speed the motor will run at under the rated load. Specifically, in the table above, the number in the RPM column is the speed of the motor when 5 horsepower is being extracted from the output shaft. As the motors unload, their speed will increase and approach the synchronous speed of the rotating field that exists in their stator windings.  The rotational speed of the stator field is function of the number of motor poles and the distribution frequency of the utility system that is serving it (60 Hz in the USA and 50 Hz in most of the rest of the world).

All of the motors in the table are 4 pole motors with a synchronous speed of 1,800 rpm when operating on 60 Hz power system. The difference between the synchronous speed in the motor's stator windings and the actual speed of the motor output shaft is called slip.  Slip is the mechanism by which the motor generates torque and is able to do work and will vary as a function of load. If there were no slip, a squirrel cage induction motor would not be able to generate torque.

The graph below illustrates this phenomenon using some test data I happen to have for a 25 hp motor.

The amount of slip required to generate a given amount of torque is a function of a number of motor design and operating parameters. Thus, different motors from different manufacturers will have different operating speeds at full load, as can be seen from the table. The primary differences between the published data for two motors I looked at to assess the potential energy savings associated with a best available efficiency motor selection are: 

The one highlighted in red has a full load speed of 1,750 rpm, has a power factor of .80, and a list price of $657 where as,

The one highlighted in lavender has a full load speed of 1,760 rpm, a power factor of .84, and a list price of $448.

Both motors have the same published efficiency of 92.2%. And given the better power factor and lower price of the motor highlighted in lavender, you would be tempted to purchase that one, anticipating the same energy savings as would be produced by the other for less capital cost with the added benefit of improved power factor.

So why is it that the seemingly more desirable motor does not save as much energy as the more expensive, lower power power factor motor? It's because it will operate at a slightly higher speed than the other motor and as a result, will tend to spin the pump's impeller a bit faster than the one with the lower full load speed. If you spin the pump's impeller faster, it does more work by moving a bit more water at a bit more of a pressure difference simply because that's how a centrifugal machine works. The faster you spin the impeller (with-in the physical constraints of the design), the higher the centrifugal force generated will be, which translates into more energy transfer to the fluid stream to be converted to pressure as well as more fluid moving through the impeller.

MotorMaster accommodates this phenomenon by providing a "Centrifugal Load" check-box (see the red arrow in the figure below) that, when selected, adjusts the projected performance of the new motor based on its speed relative to the original motor.

If one recognizes this during the design process and selects the pump based on the actual motor speed, not a nominal speed, then you can have the best of both worlds. But, if the situation is a retrofit application, where the energy baseline has already been established by the pump running with a motor at 1,750 rpm, then replacing the motor with a new motor that has a higher efficiency rating but operates at a higher speed may not generate the anticipated savings if the impact of the speed change has not been taken into account and accommodated.

To accommodate the extra speed you, you might consider trimming the pump impeller slightly to modify its performance or even install a variable speed drive to slightly slow the pump down and thus ensure that the new motor would only have as much power extracted from it as the old motor did, and thus generate the intended energy savings. But, there is no free lunch in the world of physics; the impeller trim would likely reduce the efficiency of the pump slightly and the drive would introduce efficiency losses of its own. So, the minor adjustments you might consider to keep all things equal would actually not keep all things equal and you still would not see the anticipated savings even though the modifications set the pump up to deliver the same head and flow (water horsepower) as it was delivering before the motor swap.

After considering all of this, you would likely conclude that you will be better off buying the more expensive motor and realizing the maximum energy savings benefit, assuming there is no financial benefit associated with the improved power factor  and you don't need a bit more capacity out of the pump.  (Bear in mind that the motor is only a small component of the over-all facility power factor and just because you make an improvement in a small motor does not mean there will be a commensurate change in the over-all facility power factor.)

The following table contrasts the future value of the energy savings benefits of the three options I've explored relative to the baseline.

Interestingly enough, the motor with the best simple payback also delivers the least savings because it sacrifices some of the energy it saves to the pumping system due to its higher operating speed.  In contrast, the $157 premium paid for the red best efficiency selection pays for itself many times over during its lifetime especially when one recognizes that energy savings generally also translate to lower power plant emmissions.   In addition, iit is likely that energy prices will increase over the motor's operating life and the annual savings and future value will increase as well.

The bottom line is that subtle differences between motors can make a big difference in the results you get when you apply them to a given load.  If you don't recognize that up front, then you may not achieve your goal, be it energy savings, power factor improvement, or both. MotorMaster can be a very useful tool to help you take everything into account and make the right decision when contemplating a motor replacement or substitution.


Posted by David Sellers on August 18, 2008 | Comments (2)


August 25, 2008
In response to: Motor Optimization; Same Efficiency + Different Slip = Different Savings
Laszlo Weress commented:

I would like to point out that motors seldom are sized at full load. Motor efficiency will be different at lower loads and higher speed, sometimes lower, but sometimes higher. So using Motor Master, the actual savings numbers will be lower and could even produce the opposite results of two different motors. I would correct the speed v.s. load curve as motors can not run at sycnhronous speed AND different motors will have different no-load-speed.




August 28, 2008
In response to: Motor Optimization; Same Efficiency + Different Slip = Different Savings
David Sellers commented:

Hi Laszlo, Thanks for your comments. I think you and I are on the same page here. My point was exactly what you discuss in your comment. Generally speaking, motors are seldom connected to loads that actually match their nameplate rating. As a result, the motor operates at a speed other than the rated speed. If the motor is connected to a centrifugal machine, this can actually result in an increase in power consumption which means that your savings projections will not be correct if you assumed that a new, higher efficincy motor would operate at the same speed - and thus the same load - as the motor it replaced. That will probably be the result if the motors are rated for the same speed. But if the new motor is rated at a higher speed than the motor it replaces, then the results will be skewed. I also agree that the scale and resolution of the graph makes the curve look suspect. But in fact, the Gould data it is based on says that the motor approaches, but never meets syncronous speed. I recently observed this in the field when we strobed a 5 hp motor serving a 2-1/2 hp load in the form of a pump. As we throttled the pump the motor (rated at 1745 rpm with a 5 hp load) went from about 1770 rpm to about 1790 rpm. Thus, it not inconcievable to me that it would approach syncronous speed with in an rpm or two if I were to disconnect it from the load it served.





POST A COMMENT
Display Name or Registered Users Login Here.
Please restrict submissions to less than 7,000 characters (including any HTML formatting).

Before submitting this form, please type the characters displayed above. Note the letters are case sensitive:


Advertisement

Advertisements





©2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
Use of this Web site is subject to its Terms of Use | Privacy Policy
Please visit these other Reed Business sites

ADVERTISEMENT
You will be redirected to your destination in few seconds.