Sorting Out the Interconnect Standard for Distributed Generation's Future

By Gerard L. Gustafson, Applications Engineer and Gerald F. Johnson, P.E., Marketing Manager, Basler Electric, Richmond, Va. -- Consulting-Specifying Engineer, 11/1/2003

Editor's Note: The following is excerpted from the article "Intertie Requirements for DGs Connected to Radial Distribution Feeders," which appears in full in the EGSA supplement accompanying this issue of CSE.

Distributed generation is attracting more attention as a way to ensure local power supply and add to utility-system resources. However, ensuring safe, reliable operation of distributed generators (DGs) requires close attention to this equipment's connection to both utility lines and a facility's internal distribution system. The Institute of Electrical and Electronics Engineers (IEEE) has developed standards for such interconnections, addressing the connection of DGs of various sizes to systems of varying complexity. IEEE Standard 1547-2003, Standard for Interconnecting Distributed Resources With Electric Power Systems, was published in June.

Distributed generation has proven to be a viable alternative to large, centralized generation plants for meeting individual facilities' electricity needs. When such systems are designed, utilities establish intertie requirements to ensure safe and reliable power delivery both within the facility and throughout the facility's utility system.

Basic intertie protection for DGs connected to radial distribution feeders includes preventing islanding—where an area has power but the surrounding area does not—of the DG, by detecting abnormal voltages and frequencies at the point where utility and facility distribution systems meet: the "point of common coupling" (POCC).

As the size of the DG increases in relation to the distribution feeder source and load, the protection required increases to include fault detection for faults on the distribution feeder. In such scenarios, current reversal in the utility-substation breaker can result, making directional protection a possible necessity.

The connection-type of the interconnecting transformer can further complicate protection requirements. Systems with an ungrounded transformer primary will require ground overvoltage protection, while systems with a grounded transformer primary will need additional overcurrent protection.

Finally, where DG power is exported onto the utility system, transfer trip relaying may be required to ensure tripping of the DG before the utility breaker recloses.

As Standard 1547-2003 evolves, with the addition of guides for application, testing and commissioning, and monitoring/information exchange/control, utilities will adjust their standards and make it easier to meet the many challenges associated with distributed generation. However, even with intertie standards becoming more defined, each distributed generation installation will still require the engineer to evaluate these applications on a case-by-case basis.

Email
Print
Reprint
Learn RSS

Talkback

We would love your feedback!

Post a comment

» VIEW ALL TALKBACK THREADS

Related Content

Related Content

 

By This Author

There are no other articles written by this author.



SPONSORED LINKS

 
Advertisement
Sponsored Links

More Content

  • Blogs
  • Podcast

Blogs


Sorry, no blogs are active for this topic.

» VIEW ALL BLOGS RSS

Podcast

Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
Cooling People, Not Buildings with John Suzukida, PE
Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
Listen Now | Download MP3 | Subscribe
» VIEW ALL PODCASTS Subscribe Now to HVAC & Building Automation and never miss an episode
Advertisements





NEWSLETTERS
Plug in and get the latest CSE news, trends and industry updates delivered directly to your inbox!

Green Scene
CSE Codes & Standards
CSE NewsWatch
CSE Fire and Life Safety Solutions
CSE Business of Engineering Management Report
CSE Electrical Solutions
CSE HVAC Solutions
Pure Power
CSE Product Showcase
©2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
Use of this Web site is subject to its Terms of Use | Privacy Policy
Please visit these other Reed Business sites