Warming Up with the Cleveland Browns

Staff -- Consulting-Specifying Engineer, 2/1/2003

Cleveland Browns Stadium plays host to more than 73,000 football fans during home games. Down on the playing field, winning may be more of a challenge at this point for the fledgling franchise than it was when Jim Brown, Otto Graham and Lou Groza were running, passing and kicking their way to victory.

But with an underground hydronic radiant heating system that keeps the playing field from freezing in the face of icy winds off of Lake Erie, the new generation of Browns find it easier to keeping their footing.

Contractors installed 210,000 ft.—nearly 40 mi.—of 3/4-in. PEX tubing divided into four zones, each with 189 loops. The tubing is installed on 6-in. centers, 10 in. below the playing surface.

A solution of 40% inhibited ethylene glycol-based heat transfer fluid and water circulates through the underground system. Nine gas-fired boilers feed 7,000 gals. of the solution to the field through two primary pumps and eight secondary pumps. The boilers heat the solution to 180°F. Solution temperature to each zone is 140°F. The flow rate is controlled to keep the temperature at the root zone between 60°F and 65°F.

Two-way protection

While the glycol solution keeps the playing field from freezing, another heat-transfer solution protects the stadium's cooling system throughout the winter.

"The cooling system is not a conventional design, where you have the chiller indoors and a cooling tower outside to enable easy draining," says Jerry Zelenka, project mechanical engineer for URS, the Cleveland-based firm that designed the mechanical and electrical systems. "The life-cycle study we conducted indicated that outside air-cooled chillers, combined with electric heat, provided the best cooling and heating combination overall."

The chilled water is fed to air-handling units up to 1,000 ft. away from the chillers via an extensive system of 6- to 12-in.—mostly Schedule 40—steel piping. The piping branches out around the stadium on two sides, then up vertical shafts. A major consideration involved drainage. Draining even portions of the system during the winter months, when the cooling system is not required to operate, could be inconvenient, time-consuming and uneconomical. In addition, the cooling system also needed to be available for operation through the late fall, to satisfy any mechanical cooling requirements that might prove necessary for special events held at that time in the large club areas.

With these factors in mind, URS decided to use an industrially inhibited glycol-based solution year-round as a preventative against freezing. It also makes the system available to accommodate event scheduling right through the fall.

To help keep things cool in the summer and fall, approximately 15,000 gals. of a solution of 40% heat-transfer fluid and water are circulated throughout the system according to schedules set by a central building management system. Chillers are cycled on and off depending on facility demand.

During the winter, the cooling system normally remains shut down, its piping and system components protected from freezing by the glycol-based solution.

Email
Print
Reprint
Learn RSS

Talkback

We would love your feedback!

Post a comment

» VIEW ALL TALKBACK THREADS

Related Content

Related Content

 

By This Author



SPONSORED LINKS

 
Advertisement
Sponsored Links

More Content

  • Blogs
  • Podcast

Blogs


Sorry, no blogs are active for this topic.

» VIEW ALL BLOGS RSS

Podcast

Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
Cooling People, Not Buildings with John Suzukida, PE
Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
Listen Now | Download MP3 | Subscribe
» VIEW ALL PODCASTS Subscribe Now to HVAC & Building Automation and never miss an episode
Advertisements





NEWSLETTERS
Plug in and get the latest CSE news, trends and industry updates delivered directly to your inbox!

Green Scene
CSE Codes & Standards
CSE NewsWatch
CSE Fire and Life Safety Solutions
CSE Business of Engineering Management Report
CSE Electrical Solutions
CSE HVAC Solutions
Pure Power
CSE Product Showcase
©2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
Use of this Web site is subject to its Terms of Use | Privacy Policy
Please visit these other Reed Business sites