Multi-Purpose Comfort for Multi-Use Stadium

Staff -- Consulting-Specifying Engineer, 1/1/2002

As the home of four professional sports teams, the Staples Center in Los Angeles can experience up to 10 days each season where multiple events occur on a single day. Therefore, its 35-person crew needs to be able to change the venue from hockey to basketball in less than two hours, including installation or removal of extra seating.

The facility's seating, concessions, lighting and sound systems were all designed to maximize a visitor's experience. Not so obvious to the spectators, but just as important for their comfort, is the HVAC system.

'Chill out' in L.A.

M.E. Engineers/Hayakawa Associates of Los Angeles designed a system that includes low chilled-water and supply-air temperatures and features three high-efficiency 833-ton chillers using HCFC-123. Cooling towers for the units are based on an 82.5°F to 94.6°F range and operate on a 2.3 gpm/ton flow rate. This design improves overall system efficiency by reducing pump and fan power requirements over more traditional 3.0 gpm flow rates.

The centrifugal chillers deliver chilled water in the range of 40°F to 42°F to the air handlers for most arena events, and at 36°F for hockey games and ice rink shows. Lower chilled-water temperatures during rink events assures dehumidification to help maintain the surface quality of rink ice. With this low temperature water, supply air is delivered to the space at 40°F for ice rink events and at 45°F for others.

In addition to the centrifugal units, a 300-ton screw chiller is used when chilled-water demand is low, typically at times when the arena is not in use.

Air handlers, with 12-row chilled-water coils, are the main source of dehumidification of building air. Other types of air handlers supply restaurants, retail areas, locker rooms and office areas.

In addition to general seating areas, there are 160 luxury suites, each with variable-air-volume boxes and electric reheat and ventilation air provided by a dedicated duct system.

Acoustical comfort

Guaranteeing the right climate is the major challenge for the HVAC system, but acoustical comfort is also a significant issue for HVAC designers. "We book a wide range of events, not just sports contests," explains Bill Pottorff, the facility's chief engineer. "It's important that ambient sound be held as low as possible."

In this respect, Pottorff says, the acoustical and comfort levels produced by the facility's plant has exceeded all expectations.

Email
Print
Reprint
Learn RSS

Talkback

We would love your feedback!

Post a comment

» VIEW ALL TALKBACK THREADS

Related Content

Related Content

 

By This Author



SPONSORED LINKS

 
Advertisement
Sponsored Links

More Content

  • Blogs
  • Podcast

Blogs


Sorry, no blogs are active for this topic.

» VIEW ALL BLOGS RSS

Podcast

Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
Cooling People, Not Buildings with John Suzukida, PE
Senior Editor Amara Rozgus (pictured) speaks with John Suzukida, PE, president of Lanex Consulting LLC, Shoreview, Minn. This conversation is about the role of electricity in the future and zoned heating and cooling.
Listen Now | Download MP3 | Subscribe
» VIEW ALL PODCASTS Subscribe Now to HVAC & Building Automation and never miss an episode
Advertisements





NEWSLETTERS
Plug in and get the latest CSE news, trends and industry updates delivered directly to your inbox!

Green Scene
CSE Codes & Standards
CSE NewsWatch
CSE Fire and Life Safety Solutions
CSE Business of Engineering Management Report
CSE Electrical Solutions
CSE HVAC Solutions
Pure Power
CSE Product Showcase
©2008 Reed Business Information, a division of Reed Elsevier Inc. All rights reserved.
Use of this Web site is subject to its Terms of Use | Privacy Policy
Please visit these other Reed Business sites